INSTALLATION AND USE INSTRUCTIONS

12

4- INSTALLATION

C260

GENERAL INSTRUCTIONSI

• 

L’installazione dell’attuatore deve essere eseguita esclusivamente da personale tecnico competente e qualifi cato in possesso de

• 

The actuator installation can be performed exclusively by competent and qualifi ed technical personnel satisfying the professional 

and technical requirements fore seen by the laws in force in the country of installation.

• 

The actuator performance must be suffi  cient to assure the correct movement of the window. It is compulsory to verify the thrust or 

tractive force according to the type and weight of the window. It is forbidden to exceed the limits concerning technical data (cap 3).

• 

The actuator installation must be performed exclusively with closed window.

• 

Before performing the installation of the actuator on bottom hung windows, verify that on both sides of the window two compass 

stroke limit devices are installed in order to avoid the accidental fall of the window.

• 

For correct operation of the actuator, the window frame must have a minimum height value included in the range stated in par 3.

• 

Verify that distance “D” between the actuator shell and the chain end is greater than 5 mm.

• 

The fi tting surface for the brackets must be perfectly fl at and/or smooth.

• 

Check the adequacy of the window and the suitability of the materials of the window and/or frame on which the actuator will be fas-

tened. And it must ensure a good support of the actuator-window assembly during the movement.

INSTALLATION

• 

Perform the installation as described in Chapter 5 : INSTALLATION INSTRUCTIONS / FIGURES.

ELECTRIC CONNECTIONS

• 

The electric connection of the actuator (Cap.6) can be performed only by competent and qualifi ed technical personnel foreseen by 

the law in force in the country of installation who can issue to the customer a declaration of conformity for the connection and/or 

plant carried out.

• 

Before performing the electric connection of the actuator, verify the correct installation on the window

• 

The mains to which the actuator is connected must comply with the requirements of the laws in force in the country of installation, 

as well as satisfy the technical features given in Cap.3 and on the rating plate and the “CE” marking.

• 

The section of the mains cables must be properly sized according to the absorbed electric power (see rating plate and “CE” marking).

• 

Any type of electric material (plug, cable, terminals, etc.) Used for the connection must be suitable for the use, with “CE” marking, 

and complying with the requirements foreseen by the laws in force in the country of installation.

• 

To assure an effi  cient separation from the mains, it is compulsory to install upstream of the device a temporary bipolar switch (push-

button) of approved type. Upstream of the command line, it is compulsory to install an unipolar main switch with opening of contacts 

of at least 3 mm.

• 

Before making any electrical connections on the actuator, make sure the power supply cable is not damaged. If the cable is dam-

aged, then it must be replaced by the manufacturer through the technical assistance service or by technical operators.

ELECTRIC CONNECTIONS DEVICES

THE CONTROL DEVICES USED TO DRIVE THE ACTUATOR MUST ASSURE THE SAFETY CONDITIONS FORESEEN BY 

THE LAWS IN FORCE IN THE COUNTRY OF USE.

According to the diff erent type of installations, the actuators can be driven by the following control devices:

1) MANUAL PUSH-BUTTON:

Bipolar switch button with central OFF position, with biased-off  switch;

2) OPTIONAL: CONTROL AND FEEDING UNIT:

TOPP microprocessor control units (e.g.: Mod. TF, etc.) controlling the single actuator or more than one actuator simultaneously by 

means of one or more manual pushbuttons, an infrared remote control or a 433 Mhz radio control. To these control units, it is possible to 

connect rain sensors (RDC - 12V), wind sensor (RW) and brightness sensor.

•  To assure a correct operation of the actuator, the command and feeding units eventually used have to provide power 

supply to the actuator for max. 120 sec.

•  Before operating the actuator, the user must compulsorily verify that near and/or under the window there are not any 

person, animal and thing whose safety may be accidentally jeopardised

CORRECT ASSEMBLY OF THE ACTUATOR

• 

The correct adjustment of the window frame closing assures the life and the tightness of the seals, as well as the good operation of 

the actuator.

• 

With open window frame, verify that the stroke is some centimetre lower than the stroke limited by window frame mechanical limit 

devices;

• 

Verify that the chain coupling (A) is on the same axis of the chain end (B). Otherwise, loosen the tightening screws and position 

correctly. When the devices are not coaxial, damages to the actuator and the window frame may arise.

Содержание C260

Страница 1: ... FOR WINDOW AUTOMATION EN BEFORE INSTALLING AND USING THE ACTUATOR IT IS COMPULSORY FOR THE INSTALLER AND THE USER TO READ AND UNDERSTAND THIS MANUAL IN ALL ITS PARTS THIS MANUAL IS INTEGRAL PART OF THE ACTUATOR AND MUST BE PRESERVED FOR FUTURE REFERENCE UNTIL DEMOLITION OF THE SAME ...

Страница 2: ......

Страница 3: ...COMPONENTS PAG 9 APPLICATIONS PAG 11 TOP HUNG outward opening application PAG 14 BOTTOM HUNG outward opening application PAG 16 BOTTOM HUNG inward opening application PAG 18 VERTICAL outward opening application PAG 20 ACTUATOR ON LEAF inward opening application PAG 22 SIDE HUNG Outward opening PAG 24 SIDE HUNG Inward open PAG 27 ELECTRICAL CONNECTIONS PAG 30 INDEX ...

Страница 4: ...INSTALLATION AND USE INSTRUCTIONS 4 C260 EC DECLARATION OF INCORPORATION ...

Страница 5: ...mal conditions by using the relative controls He she must also be able to operate with the actuator under maintenance in order to perform simple routine maintenance operations cleaning and start or reset the actuator following an unscheduled stop SAFETY GENERAL INSTRUCTIONS Operators must be informed of accident risks safety devices and the general accident prevention regulations established by in...

Страница 6: ...g type model serial number and year of construction of the actuator In case of replacement of the power supply cable it is necessary to use a cable type h05 vvf 3 x 0 75 The replacement can be performed exclusively by competent and qualified technical personnel meeting the professional and tech nical requirements foreseen by the laws in force in the country of installation MAINTENANCE If the actuat...

Страница 7: ...ontrol device the user has to compulsory occupy a safe control position assuring visual control on the window movement It is compulsory to verify constantly in time the functional efficiency and the rated performance of the actuator of the window frame where it is installed and of the electric plant performing when necessary interventions of routine or supplementary maintenance assuring operation co...

Страница 8: ...he actuator out of reach of children RATING PLATE AND CE MARKING The CE marking certifies the compliance of the machine with the essential safety and health requirements foreseen by the product European Directives The rating plate is an adhesive plate in polyester silk screen printed in black having the following size L 24 mm H 60 mm It is applied externally on the actuator The plate bears in reada...

Страница 9: ...C260 TECHNICAL DESCRIPTION 3 INSTALLATION AND USE INSTRUCTIONS 9 COMPONENTS A B C D E ...

Страница 10: ...INSTALLATION AND USE INSTRUCTIONS 10 3 TECHNICAL DESCRIPTION C260 COMPONENTS DIMENSIONING ...

Страница 11: ... application S3 SG M2 1000 VERTICAL outward opening application S4 SH M1 800 SIDE HUNG outward opening application LEFT S2 SF PF M1 600 SIDE HUNG outward ope ning application RIGHT S4 SF PF M1 600 SIDE HUNG inward opening application LEFT S3 SF LF M2 1000 SIDE HUNG inward opening application RIGHT S3 SF PF M2 1000 ON LEAF On the window inward opening application S4 SD M1 950 Distance from the open...

Страница 12: ...ables must be properly sized according to the absorbed electric power see rating plate and CE marking Any type of electric material plug cable terminals etc Used for the connection must be suitable for the use with CE marking and complying with the requirements foreseen by the laws in force in the country of installation To assure an efficient separation from the mains it is compulsory to install up...

Страница 13: ...d to the window to avoid damaging it If this happens in the last 50mm of the movement which is below the allowable maximum overlap you might find that the window remains slightly open the next time it is closed You only need to briefly open and close the window a few times about 4times to activate the system and restore the window to its correct and proper closure Detailed description for restoratio...

Страница 14: ...INSTALLATION AND USE INSTRUCTIONS 14 5 INSTALLATION INSTRUCTIONS FIGURE C260 Stroke 600 230V Standard TOP HUNG outward opening application Double push point ...

Страница 15: ... connections according to the provisions as well as with reference to the wiring diagram Power the actuator and let the chain come out for at least 250mm of stroke then disconnect the actuator 7 8 First fasten the LEFT chain terminal to the S2 first fit the long side of the shaft and then in sert the entire assembly Move the square plate to the centre of the mount and hand tighten bolt A Now insert ...

Страница 16: ...INSTALLATION AND USE INSTRUCTIONS 16 5 INSTALLATION INSTRUCTIONS FIGURE C260 Stroke 600 230V Standard BOTTOM HUNG outward opening application Double push point ...

Страница 17: ...c connections accor ding to the provisions as well as with reference to the wiring diagram Power the actuator and let the chain come out for at least 250mm of stroke then disconnect the actuator 7 8 First fasten the RIGHT chain terminal to the S2 first fit the long side of the shaft and then in sert the entire assembly Move the square plate to the centre of the mount and hand tighten bolt A Now inse...

Страница 18: ...INSTALLATION AND USE INSTRUCTIONS 18 5 INSTALLATION INSTRUCTIONS FIGURE C260 Stroke 600 230V Standard BOTTOM HUNG Inward opening Double push point ...

Страница 19: ...ndow brackets are correctly fastened to their clamps 7 Perform the electric connections according to the wiring diagram Power the actuator and let the chain come out for at least 150mm of stroke then disconnect the actuator Fit the actuator into the clamps M2 through the tracks on the actuator Centre the chain end on the bottom hinged bracket 8 Fasten the chain terminal to the bottomhinged Bracket...

Страница 20: ...INSTALLATION AND USE INSTRUCTIONS 20 5 INSTALLATION INSTRUCTIONS FIGUR C260 Stroke 600 230V Standard VERTICAL outward opening application Double push point ...

Страница 21: ... to the provisions as well as with reference to the wiring diagram Power the actuator and let the chain come out for at least 250mm of stroke then disconnect the actuator 6 First fasten the RIGHT chain terminal to the S4 first fit the long side of the shaft and then insert the entire assembly Move the square pla te to the centre of the mount and hand tighten bolt A Now insert bolt B included into th...

Страница 22: ...INSTALLATION AND USE INSTRUCTIONS 22 5 INSTALLATION INSTRUCTIONS FIGURE C260 Stroke 600 230V Standard ON LEAF inward opening application Double push point ...

Страница 23: ...ic connections according to the provisions as well as with reference to the wiring diagram Power the actuator and let the chain come out for at least 250mm of stroke then di sconnect the actuator 7 8 First fasten the LEFT chain terminal to the S4 first fit the long side of the shaft and then insert the entire assembly Move the square pla te to the centre of the mount and hand tighten bolt A Now inse...

Страница 24: ...INSTALLATION AND USE INSTRUCTIONS 24 Stroke 600 230V Standard SIDE HUNG outward opening application SIDE HUNG outward opening application 5 INSTALLATION INSTRUCTIONS FIGURE C260 ...

Страница 25: ...ISTRUZIONI PER L INSTALLAZIONE E L USO 25 C260 5 INSTALLATION INSTRUCTIONS FIGURE ...

Страница 26: ...ring diagram Power the actuator and let the chain come out for at least 250mm of stroke then disconnect electri cally the actuator 7 8 First fasten the UPPER chain terminal to the S2 S4 first fit the long side of the shaft and then insert the entire assembly Move the square pla te to the centre of the mount and hand tighten bolt A Now insert bolt B included into the fra me mount and tighten both bol...

Страница 27: ...INSTALLATION AND USE INSTRUCTIONS 27 Stroke 600 230V Standard SIDE HUNG inward opening application SIDE HUNG inward opening application C260 5 INSTALLATION INSTRUCTIONS FIGURE ...

Страница 28: ...ISTRUZIONI PER L INSTALLAZIONE E L USO 28 5 INSTALLATION INSTRUCTIONS FIGURE C260 ...

Страница 29: ...Perform the electric connections according to the wiring diagram Power the actuator and let the chain come out for at least 150mm of stroke then disconnect the actuator Fit the actuator into the clamps M2 through the tracks on the actuator Centre the chain end on the bottom hinged bracket Fasten the chain terminal to the bottomhinged Bracket S3 wing with the screw and nut provi ded in the package ...

Страница 30: ...INSTALLATION AND USE INSTRUCTIONS 30 C260 6 ELECTRICAL CONNECTIONS ...

Страница 31: ......

Страница 32: ...TOPP S r l Società a Socio Unico soggetta a direzione e coordinamento di 2 Plus 3 Holding S p a Via Galvani 59 36066 Sandrigo VI Italia Tel 39 0444 656700 Fax 39 0444 656701 Info topp it www topp it ...

Отзывы: