Tollco WaterFuse Apartment Скачать руководство пользователя страница 9

9(16)

they are replaceable and so that any leaking water can be easily detected. The 
units must be installed in rooms with a waterproof floor, in a distribution cabinet, 
or in a custom space. If a distribution cabinet is used, the installation instructions 
for this must be followed. After mounting, the installation must be checked for 
leaks with the tap water installation's existing water pressure according to the 
instructions on www.säkervatten.se

Central unit: (art. no. 2220082)

Mount in a suitable place near the motorised ball valve.

 

The box has a "button" on the underside that is used to open it. 

 

Do not install inside a metal water distribution cabinet as this will weaken 
the radio signals to the wireless units.  

 

The supplied DC adapter can be used for power supply or if the property 
has 12vdc, it is connected via a terminal block on the circuit board. 
The cable from the motorised ball valve is drawn to the central unit and 
connected to the 6-pole terminal K80 on V1 and V2 with the red cable to +.  The 
cable from the water sensor goes to the central unit where it is plugged in to Prb 
on terminal block K81. All cables can be connected at the back of the central unit 
to avoid visible wiring, disconnect the centre plate on the mounting plate and 
connect the cables to the terminals. See Section 2.5.

Water sensor:

The supplied water sensor is placed in the water distribution cabinet and 
connected to terminal K81, Prb. Alternatively, connect to the contact on the 
bottom of the unit.

Water detector: (art. no. 2220042)

The accompanying sensors are placed in the area intended to be 
protected. For example by the dishwasher and sink: One sensor on the 
tray that should be underneath the dishwasher, one sensor on the floor 
underneath the sink and the final sensor in the shaft where the pipes 
emerge from the floor. For more installation suggestions, see section 
1.2.

 

The box has a "button" on the underside that is used to open it. Install 
two new AA batteries in the battery compartment as instructed. The 
back piece is screwed to the wall. Check that there are no electrical cables or 

"Button"

Содержание WaterFuse Apartment

Страница 1: ...1 16 WaterFuse Apartment User Manual Installation Instructions...

Страница 2: ...duct may only be connected by a qualified installer The warranty does not cover repairs of faults caused by faulty installation or incorrect use of the appliance The ball valves have been tested by Si...

Страница 3: ...1 4 Alarm 7 1 5 Faults 7 1 6 External Control 7 2 Installation Instructions 8 2 1 General 8 2 2 Installation 8 2 3 Settings 10 2 4 Connection to Alarm 11 or Other Remote Controls 2 5 Connecting the Ca...

Страница 4: ...water distribution cabinet and wireless water detectors can be placed under the dishwasher or sink The water detectors function as a smoke alarm but with water If they indicate water a signal is sent...

Страница 5: ...ndicator next to the knob shows open closed Fitted in the water distribution cabinet Water sensor The water sensor is placed in the water distribution cabinet and when water is indicated the control u...

Страница 6: ...touch water in case of a leak resulting in rising water level for example in the threshold 1 3 Daily Operation Monitoring of the water system takes place continuously and no daily measures need to be...

Страница 7: ...ng normal use the batteries have a life expectancy of at least 2 years Radio communication errors If the radio communication between different devices stops working or does not work satisfactorily thi...

Страница 8: ...mote devices and water detectors A washing machine can be placed in the kitchen without a floor drain if there is a waterproof surface and a water detector connected to a water switch by wire or wirel...

Страница 9: ...the 6 pole terminal K80 on V1 and V2 with the red cable to The cable from the water sensor goes to the central unit where it is plugged in to Prb on terminal block K81 All cables can be connected at...

Страница 10: ...s screwed to the wall Check that there are no electrical cables or installations within 50 cm of the device as this impairs the radio transmission 2 3 Settings There are a number of settings that can...

Страница 11: ...t on and off automatically The input port uses optocouplers to protect the electronics Suggestion for connection to external controls Jumper Out with Ext Install switch between Ext and 0v When the swi...

Страница 12: ...nal block K80 Ball valve 1 is connected to V1 Red on Ball valve 2 is connected to V2 Red on External voltage supply between 12 24 and 0v Terminal block K81 Water sensor between Prb and Prb External co...

Страница 13: ...te plug in the batteries the unit beeps the installation mode automatically switches to normal mode after 5 minutes When the control unit receives the installation signal ON flashes green Press ON to...

Страница 14: ...15 G20 DN15 DN20 2 AA 1 5v batteries for remote unit Motorised ball valves with manual override 2 AA 1 5v batteries for water detector Battery life is expected to exceed 2 years Radio transmission up...

Страница 15: ...cable This means that shipping costs inspection and assem bly costs are not included in the warranty commitment If possible use the original packaging if the product needs to be transported The transp...

Страница 16: ...16 16 Tel 018 349010 info tollco se www tollco se Tollco AB Rubanksgatan 4 741 71 Knivsta...

Отзывы: