background image

Psge 03

VI. Mounting dimension

Front

Side

Mounting 

96

48

88.5

100

44

91

45

30

25

+0.5
-0

+0.5
-0

1

It is suggested that the meter gets on power for 15 minutes before measuring.

2

Working environment is 0

50

℃,

humidity below 85%RH.

3

The calibration interval for this meter is one year.

4

Please keep the meter from shaking and shocking. Don’t place the meter in the environment full of excess dust and hazard chemicals and gas.

5

If the meter is not used for long time, please get on power every 3 months, each time not less than 4 hours.

6

To be stored in the environment at 0

50

, humidity below 60%RH, no direct sunshine. The meter should not contact with organic solvent or oil.

VII. Notice for use and storage

The second alarm hysteresis:
It is similar to HY1.

Lock key
Lock=000,read and write
Lock=010,read only

Power On

Power supply

 ON

All LED
are on

Measuring 
Status

Measuring status operation setting

Input Channel Selection:
Chosen from "IN1

IN3"

The first alarm mode:
H

High

L

Low

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

The first alarm value setting

The second alarm mode:
It is similar to Ad1.

The first alarm hysteresis. For
example, if Ad1 is H, AL1=50,HY1=5,
when measuring value

50(AL1), alarm

is active; when it is

45(AL1-HY1),

alarm is not active.

The second alarm value setting:
It is similar to AL1

Current Transforming: it is only for
5A range or 75mV spliter current input. 
If its value is set as the the ratio of external 
CT or spliter, the actual range should be CT*5. 
For other situation, CT is set as 1.

Amendment value,displaying value =
measured value +PS,factory setting:
PS=0

Communic:ation baud rate:
4.8kbps

9.6kbps for option.

Add

Meter communication address

Analog output low limit setting:
when measured value = rL set value, 
the corresponding analogue output is 4mA

Analog output high limit setting:
when measured value = rH set value, 
the corresponding analogue output is 20mA

VIII. Communication

         This meter using Modbus RTU communication protocol, and it can run RS485 half-duplex communication. Read function code is 0x03, write function 

code is 0x10, 16-bit CRC checking is applied. The meter don’t  feedback error message. The communication data type is 32 bit integer data, true code stands 

for positive number, complemental code stands for negative number, data rate is 0.001

for example, if the meter data received by host is 5000, then meter 

data * rate = original data (5000*0.001=5.000). Therefore, when host writes meter, the data should multiply by rate 1000 before it is sent to the meter. 

Data Frame format

Start bit

Data bit

Stop bit

Check bit

NO

1

8

1

Handling of abnormal communication

       If there is abnormal response put the function code on the top position 1. For example: Host request the function code 0x03,and the response function 

code from slave should be 0x83.

Error type code

0x02---Data location error

the request data location from host computer exceeds the range of the meter.

0x03---Data value error

the data value sent by host computer exceeds the data range of the meter.

CRC check error, function code error, don’t return value. 



1. Read Multiple Registers

For example: The host computer read AL1

1st alarm value 5.0

Address code of AL1 is 0x0000

32bit

4 byte

),

seizes 2 data registers; hexadecimal  memory code of 5.0*1000=5000 is 0x00001388.

Host request

read multi-register

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

9

8

Meter Add Function Code Start address high  

bit

Start address low 

bit

Data bytelength high 

bit

Data byte length low 

bit

CRC code low bit CRC code high bit

0x01

0x03

0x01

0x03

0x04

0x00

0x00

0x00

0x13

0x88

0xF7

0x65

0x00

0x00

0x02

0xC4

0x0B

Slave normal answer(Read multi-register)

Data byte number Data 1 high bit Data 1low bit Data 2 high bit Data 2 low bit CRC code low bit CRC code  high bit

Meter Add Function Code



Отзывы: