IP-EN1-EB Instruction Manual
1
Instruction Manual
Indication Panel for mandatory indications
of EN 54-16 for VX-2000 and SX-2000
IP-EN1-EB
1134
TOA Electronics Europe GmbH
Süderstrasse 282, 20537 Hamburg, Germany
14
1134 - CPR - 102
1134 - CPR - 110
EN 54-16: 2008 Fire detection and fire alarm systems - Part 16:
Voice alarm control and indicating equipment
■
Description
The indication panel IP-EN1-EB is designed to provide the mandatory indications as
required by EN 54-16: 2008 for the VX-2000 and SX-2000 system. Additional 8 indicators
can be used to indicate faults in fire zones (this is an option with requirements in the EN 54-
16) or other faults (EN 54-16 requires yellow indications for faults). A buzzer sounds at
every new fault and can be silenced by depressing the acknowledge button. The lamp test
button allows checking the proper operation of all indicators and the buzzer. All faults can
be reset by using a key.
In addition to above, indication panel IP-EN1-EB provides a general fault output with a
switch-over relay that can be equipped with optional resistors for a surveillance of the
connected fire detection system (FDS) (the surveillance must be performed by the FDS). It
also provides one emergency control input that can either be activated by making/breaking
a contact or by a voltage of 12 or 24 VDC (depending on jumper setting). It supports the
change between emergency and normal mode / silence, controlled by a single contact of
the FDS. The voltage-controlled control input allows a fire detection system to monitor
connection.
The indications and controls require a certain setting in the software that will be described
in this instruction manual.
■
Precautions
Make sure that the power supply of the IP-EN1-EB is switched off or disconnected when
connecting or disconnecting wires to avoid a damage of the IP-EN1-EB.
Make sure that the jumper settings and connection to external equipment is made
correctly, otherwise it may cause malfunctions of the IP-EN1-EB or external equipment
as a fire detection system.
Make sure of right polarity when connecting the power supply and external equipment.