![TMEIC PVU-L0800GR Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/tmeic/pvu-l0800gr/pvu-l0800gr_installation-manual_1121785031.webp)
4GBG1009
PVU-L0800GR / PVU-L0840GR / PVU-L0880GR Installation Manual
30
(1) Connection of DC input bus bars
Details of DC output bus bars are shown in the outline drawing.
Fig. 13.3 DC Input terminal bus bar
Table 13.3
Conductor specifications for inverter DC input cables
POS
No. of
Conductor
Each
Conductor
(A)
AWG/kcmil
90C CU
AWG/kcmil
90C AL
Comment
4
293
300
400
1 hole
1 Conductor
6
195
2/0
4/0
1 hole
1 Conductor
8
146
1/0
2/0
1 hole
1 Conductor
NEG
No. of
Conductor
Each
Conductor
(A)
AWG/kcmil
90C CU
AWG/kcmil
90C AL
Comment
4
293
300
400
1 hole
2 Conductor
6
195
2/0
4/0
1 hole
2 Conductor
8
146
1/0
2/0
1 hole
2 Conductor
Note: Select the proper cable following applicable NEC/NFPA70 and local requirements
P