172-65464MA-02 (JH8R-B) 18 Nov 2020
8
Maintenance
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Be sure to use only the recommended components when repairing the
product, and NEVER attempt to modify the product in any way. Failure to
observe these precautions may result in damage to the product or burns
or other injury due to malfunction or the discharge of fluids.
CAUTION
Operational Check
A visual inspection of the following items should be done on a daily basis to determine
whether the product is operating properly or has failed. Periodically (at least biannually)
the operation should also be checked by using diagnostic equipment, such as a
stethoscope or thermometer.
If the product should fail, it may cause damage to piping and equipment, resulting in
faulty or low quality products or losses due to steam leakage.
Normal
: Condensate is discharged continuously, together with flash steam,
and the sound of flow can be heard. If there is very little condensate,
there is almost no sound of flow.
Blocked
(Discharge Impossible)
: No condensate is discharged. The trap is quiet and makes no noise,
and the surface temperature of the trap is low.
Blowing
: Live steam continually flows from the outlet and there is a
continuous metallic sound.
Steam Leakage
: Live steam is discharged through the trap outlet together with
condensate, accompanied by a high-pitched sound.
Flash Steam
Live Steam Leakage
Parts Inspection
When parts have been removed, or during periodic inspections, use the following table
to inspect the parts and replace any that are found to be defective.
Procedure
Gaskets: Check for warping or scratches
Screen: Check for clogging or corrosion
Float: Check for scratches or dents
Bimetal Plate, Valve Plug, Air Vent Case (Valve Seat): Check for
Scratches or damage
Body interior: Check for build-up of scale
Orifice Opening: Check dirt, oil film, wear and damage
White jet containing
water droplets
Clear, slightly
bluish jet