background image

7

INSTALLATION

• Reciprocating Saw

• 1/2", 7/16",5/8" Wrench

• Vent Pipe

• Drill and 1/8", 1/4", 1/2" Bits, 1” hole saw

• 1/4" Masonry Drill Bit

• Wire

• Blade Screwdriver

• 1/4", 5/16”, 11/32" Nut Driver/Socket

• Wire Nuts

• Wire Cutter/Stripper

• Hammer

• 1” Strain Reliefs

• Tube Cutter

• 1” Anti-Short Bushings
•  Electrical Conduit

INSTALLING VENT HOOD TERMINUS

1.  a) Fold template A along dashed line and attach in between the floor joists ensuring that it is 

snug against the sill plate and right hand floor joist.  Follow same procedure if floor trusses 

are used, (See Diagram B).

b) If the SS1R is not being installed between floor joists, attach the template to the wall it will be 

exiting ensuring it is level.

2. Using 1/2" bit, drill pilot holes noted on each side of the template from inside through rim-joist, 

wall board, siding, etc., keeping drill bit perpendicular to the wall.  1/2" bit must be long enough 
to penetrate through exterior.

3. Remove template from rim-joist and attach to building exterior, aligning pilot hole markings on 

template with holes previously created in Step #2.

4. Drill the four corner holes noted on the template through the building exterior.  Remove the 

template and mark lines from the 

outside

edge of the holes drilled, forming a rectangle.

5. Using reciprocating saw and appropriate blade, cut a rectangular open-

ing through the rim joist, wall board, siding, etc., on the lines marked in 
step 4.  The rectangular opening should be no larger than 8-3/8" in width
by 8" in height, (See Diagram C).

6. Knock out block material exposing rectangular opening through the wall.

7. Apply two  beads of exterior rated caulk approximately 3/8" in width at 

the seam of the outermost casing of the Vent Hood and the inner 
flange of the Vent Hood Terminus, (See Diagram D).

It is not recommended for the SS1R to be terminated on a wall that faces the direction of
the prevailing winds.  Backdrafts by severe winds can cause oil odors to remain in the 
structure and/or interrupt heating equipment operation.

DIAGRAM A1

DIAGRAM B

Tools required:

Materials required:

DIAGRAM C 

Содержание SS1R SIDESHOT (DISCONTINUED VERSION-PRE UC1 UNIVERSAL CONTROL) 8504046 REV 0595

Страница 1: ...RSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION OR PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE RE...

Страница 2: ...ud Weatherking and Heat Controller oil fired furnaces The SS1R automatically vents the flue gases away from the oil furnace to the outdoors By combining outside air with high tech insulation and maintaining required clearances surrounding combustible materials remain at safe temperatures A factory post purge time is set at 2 minutes and is adjustable up to 16 minutes see Pre Post purge Settings on...

Страница 3: ...he Canadian Electrical Code 2 Plan the vent layout so that the code required clearances are maintained from plumbing wiring and combustible materials 3 The SS1R motor shaft must be mounted horizontally to ensure proper operation of the Fan Proving Switch and prevent motor bearing wear 4 Flue gas temperatures must not exceed 575oF at SS1R inlet Ambient temperature must not exceed 104oF 5 Make certa...

Страница 4: ...mes Fan Prover was in electrically closed position prior to venter operation LED 4 Flashes 3 Times Fan Prover does not close within 60 seconds after call for heat LED 4 Flashes 4 Times Fan Prover did not re close after 10 minutes of Venter operation LED 4 Flashes 5 Times Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes Investigate causes of Fan Prover not...

Страница 5: ... LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR XL XN AUXILIARY DEVICE POWER TERMINALS 115 VAC Maximum of 0 15 Amps Only connect to Tjernlund auxiliary devices SEE WARNING 1 LED STATUS LIGHTS See LED Status Fault Indicator Section for details J1 J2 CALL JUMPER Used when...

Страница 6: ...ings Not to be less than 2 feet from an adjacent building The SS1R is also Listed to terminate a minimum of 12 below above or horizontally from a soffit deck or adjacent sidewall Pre Purge Post Purge Pre Cycle Prover Status Check Deactivated DIP SWITCH NUMBERING 1 ON 2 3 4 5 6 7 8 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 4 PRIOR TO SETTING 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Seconds 35 Sec...

Страница 7: ...pardize people overheat combustible structures or enter buildings A venting system shall not terminate within 1 8 m 6ft of the following A window door or mechanical air supply inlet of any building including soffit openings A gas service regulator vent outlet A combustion air inlet A property line A direction facing combustible materials or openings of surrounding buildings A venting system shall ...

Страница 8: ...e from rim joist and attach to building exterior aligning pilot hole markings on template with holes previously created in Step 2 4 Drill the four corner holes noted on the template through the building exterior Remove the template and mark lines from the outside edge of the holes drilled forming a rectangle 5 Using reciprocating saw and appropriate blade cut a rectangular open ing through the rim...

Страница 9: ...Template B to the floor joist that is to be notched aligning the sight line noted on the template with the end or the outside casing of the Vent Hood Terminus 2 Cut out notch on line shown on the template NOTCH BRACING It is recommended and local codes may dictate that the joist be reinforced as outlined below Bracing of the rim joist is not necessary 1 Cut two 2 x 4 pieces of wood 28 inches in le...

Страница 10: ... drill bit approximately 1 deep and install the screws provided to secure the bracket to the wall b If installing the bracket into a masonry wall drill 2 holes at each point established in step 3 with a 1 4 masonry drill bit approximately 1 deep Tap the masonry anchors into the holes drilled in step 4 Screw the wall bracket onto the wall 5 Connect the other end of wall support bracket to the stud ...

Страница 11: ... metal tube 5 Attach the vent pipe inlet collar to the rear inlet port making sure that the sensing tube is orientated as shown See Diagram M NOTE Alignment marks on the inlet collar and plenum casing must match 6 Attach 90 0 compression fitting to the short tube on the inlet collar 7 Using the soft aluminum tubing connect the Fan Proving Switch to the inlet collar Take care not to crimp the tubin...

Страница 12: ... INSTRUCTIONS PERTAIN ONLY TO RHEEM RUUD OR WEATHERKING D OBD XXX OPD XXX and etc and F OBF XXX OPF XXX and etc SERIES OIL BURNING FURNACES 1 All wiring from the SS1R to the oil furnace must be appropriate Class 1 wiring as follows installed in a rigid metal conduit intermediate metal conduit rigid non metal conduit electrical metallic tubing Type MI Cable Type MC Cable or be otherwise suitably pr...

Страница 13: ...ld be routed through a disconnect so that power to the SS1R can be turned off remotely if necessary Additionally all wire should be run through the appropriate conduit per NEC standards as noted in step 1 C A ground wire will need to be installed between the system ground and the grounding lug in SS1R electrical box D A neutral wire will need to be installed from the oil furnace line neutral to th...

Страница 14: ...equire a special male quick connect Amp Manufacturing part 2 520102 2 insulated male spade Do NOT cut any wires on the existing burner Also the wire connection to the Burner Motor lead should be made inside the burner junction box and should be covered and concealed by the primary control once it is replaced G Install a field constructed wire between the terminal labeled Burner Motor step E above ...

Страница 15: ...ICE In order for the SS1R pressure switch to function properly for the intended application the proper bleed orifice has to be selected as determined below 1 Upon installation if the furnace input rate is 1 gallon per hour or less 140 000 BTU hr or less then the plug should be installed in the pressure switch 2 Upon installation if the furnace input rate is greater than 1 gallon per hour or 140 00...

Страница 16: ...uipment to operate for at least five minutes Tripping of the burner circuit by the Fan Prover Switch or Limit during the five minute operation indicates an unsafe operating condition Turn fuel supply off to appliance and DO NOT OPERATE UNTIL UNSAFE VENTING CONDITION IS INVESTIGATED BY QUALIFIED SERVICE PERSONNEL 6 Turn thermostat to the off position Verify the SS1R and the burner operate for sever...

Страница 17: ...OTING ELECTRICAL PROBLEMS The following guide is intended to be used if a problem occurs during the use of the SS1R sidewall vent system It may be necessary to measure voltage during troubleshooting Extreme caution must be exercised to prevent injury If you are unable to determine the defective part with the use of this guide call your Tjernlund distributor or Tjernlund Products direct at 1 800 25...

Страница 18: ...post purge may cause limit to trip If the limit switch trips verify that the post purge setting is long enough to remove residual heat from the combustion chamber If high limit will not reset and has an open circuit replace high limit part number 950 0640 If high limit trips repeatedly do not operate the heater until the source of excessive heat has been determined and repaired For any newly estab...

Страница 19: ...nput and vent pipe lengths are not exceeded See Application Table on page 1 for capacities Check fan proving switch sensing tube for blockage Yes measured draft is at least 0 07 w c Replace fan proving switch part number 950 0750 MAINTENANCE SERVICE TECHNICIAN AND USER REQUIREMENTS 1 SS1R must be visually inspected annually 2 Verify over fire draft CO2 and smoke readings are all correct See Draft ...

Страница 20: ...eries Wheel 950 0635 SS1R Proving Switch 950 0750 High Limit Switch 950 0640 UC1 Universal Control Circuit Board 950 8804 Oil Solenoid For D series oil furnaces OBD XXX OPD XXX and etc 950 0690 Oil Solenoid For F series oil furnaces OBF XXX OPF XXX and etc Contact Rheem Prostock parts department for solenoid part number WHAT IS NOT COVERED Product installed contrary to our installation instruction...

Страница 21: ...20 SIGHT LINE LINE SIGHT TEMPLATE B C U T O U T B O U N D A R Y C U T O U T B O U N DARY ...

Страница 22: ...BACKSIDE OF TEMPLATE B ...

Страница 23: ...21 CORNER HOLES TEMPLATE A PILOT HOLES CORNER HOLES INSTRUCTIONS Rough in 8 3 8 Width 8 Height 8 Height 8 3 8 Width Rough in ...

Отзывы: