background image

9

Minimum clearances from the Plenum to any combustible materials must be maintained as listed on page 5.  Failure to do so can
cause a fire or explosion resulting in property damage, personal injury or death.

Note:

Blower - Motor/Wheel assembly can be removed to make

Plenum section easier & lighter to install.  Refer to Removal 
and Replacement of Motor/Wheel Assembly, Page 18.

1. Connect the Plenum to the Vent Hood by aligning both grooves 

on the bottom of Plenum with both grooves on the bottom of the
Vent Hood.  The Plenum is designed to slide into the Vent 
Hood, (See Diagram I).

2. Gently slide the Plenum into the Vent Hood until the slip joint 

guides located on each side of the Plenum are in contact with 

each other.

3. Slide the slip joint drivers from the bottom upward over the the slip joint guides as far as possible by hand.  A hammer may be 

used to tap the slip joint drivers to their final position.  Start the slip joint drivers on the slip joint guides with the embossed end 

facing down.  Do not force slip joints past embossing.

INSTALLATION OF WALL SUPPORT BRACKET

1. To prevent damage to the SS1R, temporarily support the bottom of the plenum (prop on ladder) while assembling the wall 

support bracket.  Assemble the wall support bracket as shown, (See Diagram J).

2. Using the prepunched holes, adjust the wall support bracket so that a 

slight pitch

is maintained for water drainage, (See 

Diagram J).

3. Use the prepunched holes on the wall bracket as a template to mark holes to be drilled into the side wall for mounting screws.

4. a) 

If installing the bracket into a wood wall, drill 2 pilot holes at each point established in step 3 with a 1/8" drill bit 

approximately 1" deep and install the screws provided to secure the bracket to the wall.

b) 

If installing the bracket into a masonry wall, drill 2 holes at each point established in step 3 with a 1/4" masonry drill bit 

approximately 1" deep.  Tap the masonry anchors into the holes drilled in step 4.   Screw the wall bracket onto the wall.

5. Connect the other end of wall support bracket to the stud on the plenum using the supplied 1/4"-20 keps nut, (See Diagram J).

INSTALLATION OF VENT PIPE 

Single wall vent pipe is not allowed in an unconditioned or unheated space.  When Installing the SS1R vent system, a barometric
draft damper control must be used.  Install the barometric draft damper as close as is practical to the SS1R with the center line of
the barometric damper not closer than 10 inches to the SS1R inlet.  Always install the draft damper in a 6” section of pipe.  The
general venting configurations are shown in diagram K.  The SS1R vent system is designed to accept 6” single wall, type”L” or
type “A” vent pipe.  When installing the vent system, it will be necessary to use the tapered reducers or increasers as shown.

Determine which inlet of the SS1R will allow for the least amount of elbows to the furnace.  When using single wall pipe, a mini-
mum clearance of 18” must be maintained between the vent pipe and combustible materials and the vent pipe must be exposed to
view for its entire length.  If this clearance cannot be maintained, type “L” or type “A” vent may be used according to its listing and
vent pipe manufacturer’s instructions.

A maximum of 10 linear feet of vent may be used to connect the SS1R to the furnace.  No more than three 90

0

elbows may be

used (two 45

elbows will be considered equivalent to one 90

0  

elbow).

DIAGRAM I

DIAGRAM J

IMPORTANT:

Adjust SS1R mounting
bracket for a slight downward
pitch towards exit terminal.

Содержание SS1R SIDESHOT (DISCONTINUED VERSION-PRE UC1 UNIVERSAL CONTROL) 8504046 REV 0595

Страница 1: ...RSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION OR PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE RE...

Страница 2: ...ud Weatherking and Heat Controller oil fired furnaces The SS1R automatically vents the flue gases away from the oil furnace to the outdoors By combining outside air with high tech insulation and maintaining required clearances surrounding combustible materials remain at safe temperatures A factory post purge time is set at 2 minutes and is adjustable up to 16 minutes see Pre Post purge Settings on...

Страница 3: ...he Canadian Electrical Code 2 Plan the vent layout so that the code required clearances are maintained from plumbing wiring and combustible materials 3 The SS1R motor shaft must be mounted horizontally to ensure proper operation of the Fan Proving Switch and prevent motor bearing wear 4 Flue gas temperatures must not exceed 575oF at SS1R inlet Ambient temperature must not exceed 104oF 5 Make certa...

Страница 4: ...mes Fan Prover was in electrically closed position prior to venter operation LED 4 Flashes 3 Times Fan Prover does not close within 60 seconds after call for heat LED 4 Flashes 4 Times Fan Prover did not re close after 10 minutes of Venter operation LED 4 Flashes 5 Times Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes Investigate causes of Fan Prover not...

Страница 5: ... LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR XL XN AUXILIARY DEVICE POWER TERMINALS 115 VAC Maximum of 0 15 Amps Only connect to Tjernlund auxiliary devices SEE WARNING 1 LED STATUS LIGHTS See LED Status Fault Indicator Section for details J1 J2 CALL JUMPER Used when...

Страница 6: ...ings Not to be less than 2 feet from an adjacent building The SS1R is also Listed to terminate a minimum of 12 below above or horizontally from a soffit deck or adjacent sidewall Pre Purge Post Purge Pre Cycle Prover Status Check Deactivated DIP SWITCH NUMBERING 1 ON 2 3 4 5 6 7 8 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 4 PRIOR TO SETTING 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Seconds 35 Sec...

Страница 7: ...pardize people overheat combustible structures or enter buildings A venting system shall not terminate within 1 8 m 6ft of the following A window door or mechanical air supply inlet of any building including soffit openings A gas service regulator vent outlet A combustion air inlet A property line A direction facing combustible materials or openings of surrounding buildings A venting system shall ...

Страница 8: ...e from rim joist and attach to building exterior aligning pilot hole markings on template with holes previously created in Step 2 4 Drill the four corner holes noted on the template through the building exterior Remove the template and mark lines from the outside edge of the holes drilled forming a rectangle 5 Using reciprocating saw and appropriate blade cut a rectangular open ing through the rim...

Страница 9: ...Template B to the floor joist that is to be notched aligning the sight line noted on the template with the end or the outside casing of the Vent Hood Terminus 2 Cut out notch on line shown on the template NOTCH BRACING It is recommended and local codes may dictate that the joist be reinforced as outlined below Bracing of the rim joist is not necessary 1 Cut two 2 x 4 pieces of wood 28 inches in le...

Страница 10: ... drill bit approximately 1 deep and install the screws provided to secure the bracket to the wall b If installing the bracket into a masonry wall drill 2 holes at each point established in step 3 with a 1 4 masonry drill bit approximately 1 deep Tap the masonry anchors into the holes drilled in step 4 Screw the wall bracket onto the wall 5 Connect the other end of wall support bracket to the stud ...

Страница 11: ... metal tube 5 Attach the vent pipe inlet collar to the rear inlet port making sure that the sensing tube is orientated as shown See Diagram M NOTE Alignment marks on the inlet collar and plenum casing must match 6 Attach 90 0 compression fitting to the short tube on the inlet collar 7 Using the soft aluminum tubing connect the Fan Proving Switch to the inlet collar Take care not to crimp the tubin...

Страница 12: ... INSTRUCTIONS PERTAIN ONLY TO RHEEM RUUD OR WEATHERKING D OBD XXX OPD XXX and etc and F OBF XXX OPF XXX and etc SERIES OIL BURNING FURNACES 1 All wiring from the SS1R to the oil furnace must be appropriate Class 1 wiring as follows installed in a rigid metal conduit intermediate metal conduit rigid non metal conduit electrical metallic tubing Type MI Cable Type MC Cable or be otherwise suitably pr...

Страница 13: ...ld be routed through a disconnect so that power to the SS1R can be turned off remotely if necessary Additionally all wire should be run through the appropriate conduit per NEC standards as noted in step 1 C A ground wire will need to be installed between the system ground and the grounding lug in SS1R electrical box D A neutral wire will need to be installed from the oil furnace line neutral to th...

Страница 14: ...equire a special male quick connect Amp Manufacturing part 2 520102 2 insulated male spade Do NOT cut any wires on the existing burner Also the wire connection to the Burner Motor lead should be made inside the burner junction box and should be covered and concealed by the primary control once it is replaced G Install a field constructed wire between the terminal labeled Burner Motor step E above ...

Страница 15: ...ICE In order for the SS1R pressure switch to function properly for the intended application the proper bleed orifice has to be selected as determined below 1 Upon installation if the furnace input rate is 1 gallon per hour or less 140 000 BTU hr or less then the plug should be installed in the pressure switch 2 Upon installation if the furnace input rate is greater than 1 gallon per hour or 140 00...

Страница 16: ...uipment to operate for at least five minutes Tripping of the burner circuit by the Fan Prover Switch or Limit during the five minute operation indicates an unsafe operating condition Turn fuel supply off to appliance and DO NOT OPERATE UNTIL UNSAFE VENTING CONDITION IS INVESTIGATED BY QUALIFIED SERVICE PERSONNEL 6 Turn thermostat to the off position Verify the SS1R and the burner operate for sever...

Страница 17: ...OTING ELECTRICAL PROBLEMS The following guide is intended to be used if a problem occurs during the use of the SS1R sidewall vent system It may be necessary to measure voltage during troubleshooting Extreme caution must be exercised to prevent injury If you are unable to determine the defective part with the use of this guide call your Tjernlund distributor or Tjernlund Products direct at 1 800 25...

Страница 18: ...post purge may cause limit to trip If the limit switch trips verify that the post purge setting is long enough to remove residual heat from the combustion chamber If high limit will not reset and has an open circuit replace high limit part number 950 0640 If high limit trips repeatedly do not operate the heater until the source of excessive heat has been determined and repaired For any newly estab...

Страница 19: ...nput and vent pipe lengths are not exceeded See Application Table on page 1 for capacities Check fan proving switch sensing tube for blockage Yes measured draft is at least 0 07 w c Replace fan proving switch part number 950 0750 MAINTENANCE SERVICE TECHNICIAN AND USER REQUIREMENTS 1 SS1R must be visually inspected annually 2 Verify over fire draft CO2 and smoke readings are all correct See Draft ...

Страница 20: ...eries Wheel 950 0635 SS1R Proving Switch 950 0750 High Limit Switch 950 0640 UC1 Universal Control Circuit Board 950 8804 Oil Solenoid For D series oil furnaces OBD XXX OPD XXX and etc 950 0690 Oil Solenoid For F series oil furnaces OBF XXX OPF XXX and etc Contact Rheem Prostock parts department for solenoid part number WHAT IS NOT COVERED Product installed contrary to our installation instruction...

Страница 21: ...20 SIGHT LINE LINE SIGHT TEMPLATE B C U T O U T B O U N D A R Y C U T O U T B O U N DARY ...

Страница 22: ...BACKSIDE OF TEMPLATE B ...

Страница 23: ...21 CORNER HOLES TEMPLATE A PILOT HOLES CORNER HOLES INSTRUCTIONS Rough in 8 3 8 Width 8 Height 8 Height 8 3 8 Width Rough in ...

Отзывы: