The Unit must be mounted plumb and level front to back and side to side.

1.  Mark a horizontal line on the wall 

using a spirit level. This line will be 
approximately 95mm below the 
location of the top face of the unit 
when fitted (excluding duct ports).

2.  Use one of the Mounting Brackets 

as a template to mark the three 
fixing hole centres.

3.  Drill holes for fixings, always use a 

fixing suited to the wall type.

4.  Fix one Mounting Bracket to the 

wall ensuring the interlocking side 
is at the top, as shown.

Mounting Bracket highlighted

Содержание auralite TP518

Страница 1: ...EN ventilation systems HRV1 25 Q Plus TP406MB HRV1 75 Q Plus TP404MB HRV2 Q Plus TP401MB HRV3 Q Plus TP402MB Heat Recovery Ventilation Units auralite TP518 LED Status Indicator Product Manual ...

Страница 2: ...s 17 auralite Wiring Diagrams 18 Wiring Diagrams 19 Wiring Diagrams 20 Wiring Diagrams 21 Notes 22 Commissioning Controls 23 Control Parameters 23 Continuous Supply Extract Speeds 24 Boost Supply Extract Speeds 24 Boost Overrun 24 Controller Reset 25 Hardware Reset 25 Maintenance Filter Replacement 26 How to Change Filters 27 auralite Filter Notification Reset 27 Cleaning Interior 28 Cleaning Exte...

Страница 3: ...appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety 6 Children should be supervised to ensure that they do not play with the appliance 7 Ensure that external grilles are l...

Страница 4: ...am details the overall size of the unit and the additional space required around the unit to allow for commissioning and future servicing and maintenance 430 295 600 600 300 100 Service Void DO NOT BOX IN UNIT All dimensions in millimetres ...

Страница 5: ...ram details the overall sizes of the units and the additional space required around the units to allow for commissioning and future servicing and maintenance 426 490 715 860 100 Service Void 300 DO NOT BOX IN UNIT All dimensions in millimetres ...

Страница 6: ... Part Number auralite Connection Filter Covers Auto Setback Speed Continuous Speed Boost Speed with Overrun Timer Summer Bypass Summer Mode Ø100 125mm Ducting Ø125 150mm Ducting Independent Adjustment of Fans Step less Fan Speed Adjustment Automatic Frost Protection HRV1 25 Q Plus TP406MB HRV1 75 Q Plus TP404MB HRV2 Q Plus TP401MB HRV3 Q Plus TP402MB GB Patent Nos GB2469254 GB2470331 GB2470528 GB2...

Страница 7: ...emote LED ventilation system status indicator designed to fit a standard UK patress or recessed backbox The indicator has six LEDs which display y y Normal Solid light Unit is running at Continuous Speed Flashing light Unit is running at Setback Speed y y Frost Unit is in Automatic Frost Protection mode y y Filter Filters require change y y Boost Solid light Unit is running at Boost Speed Flashing...

Страница 8: ...he extract and supply air flow Boost Speed is configured with Step less independent fan controls and includes an Overrun Timer variable between 0 and 60 minutes The Boost Speed can be triggered by any device which provides a volt free one way switch such as a PIR thermostat humidistat or a standard one way switch auralite Boost Alert Boost Alert is a timer designed to prevent the HRV being inadver...

Страница 9: ... the formation of ice As internal temperatures rise Automatic Frost Protection will increase the supply ventilation flow rate back to the commissioned settings Summer Mode In properties where it is desirable to reduce the supply of warm fresh air during hot weather but where full Summer Bypass may be inappropriate or not available the optional Summer Mode operation is available Summer Mode operate...

Страница 10: ...n supplied Each HRV Q Plus unit is supplied with Mounting Bracket x 2 Safety Bracket x 1 15mm Condensate Drain Olive Nut x 1 M6x10mm Pan Head screws x 4 M6 washers x 4 Transport Bungs x 4 supplied packed in Duct Ports Product Manual x 1 User Guide x 1 Any shortages or damage must be immediately reported to the supplier ...

Страница 11: ...ngs until connecting ducting Transport Bungs are fitted to prevent debris falling into the unit and causing blockages and damage The Titon HRV Q Plus is designed to be mounted on a wall or similar The mounting surface must be sufficiently strong to support the unit Consider the positioning of electrical services and the Condensate Drain when siting the unit Ensure there is sufficient access around...

Страница 12: ...y 95mm below the location of the top face of the unit when fitted excluding duct ports 2 Use one of the Mounting Brackets as a template to mark the three fixing hole centres 3 Drill holes for fixings always use a fixing suited to the wall type 4 Fix one Mounting Bracket to the wall ensuring the interlocking side is at the top as shown Mounting Bracket highlighted ...

Страница 13: ... locating the two Mounting Brackets together Ensure a positive location is made between the two Mounting Bracket 7 The Safety Bracket MUST be fitted Fix the lower Safety Bracket as shown using the remaining M6 screw washer and suitable wall fixing Packing to be used as required behind the Safety Bracket to ensure unit is level Hook onto wall bracket Safety Bracket highlighted ...

Страница 14: ... trap which must act as an air lock Must be adequately secured and be insulated with the equivalent of at least 25mm of insulating material with a thermal conductivity of 0 04 W mK if any part of the pipe passes though an unheated void Should be installed to have a minimum 5 fall from the unit Titon recommend the use of diaphragm type waste valve in place of a conventional wet trap which could dry...

Страница 15: ...orts Titon recommend that 1 Ø125mm ducting is used to connect the HRV1 25 Q Plus 2 Ø150mm ducting is used to connect the HRV1 75 2 3 Q Plus 3 A short piece of flexible ducting approximately 200mm long is used to connect the unit to the ducting system 4 Any flexible ducting used must be pulled taught 5 A minimum distance of 200mm between the HRV Q Plus unit and any sharp bends in duct work ENSURE D...

Страница 16: ...lation 8 Where ducts pass through fire barriers they must be appropriately fire stopped in accordance with the requirements of Part B of the Building Regulations for England Wales 9 A ducting condensate drain must be fitted to vertical To Atmosphere duct work 10 Ducting must be installed in such a way that resistance to airflow is minimised 11 Ducting connected to the From Atmosphere To Atmosphere...

Страница 17: ...eparation of at least 3mm 5 HRV1 25 Q Plus HRV1 75 Q Plus HRV2 Q Plus are suitable for 230V 50 60Hz single phase with a fuse rating of 3A 6 HRV3 Q Plus suitable for 230V 50 60Hz single phase with a fuse rating of 5A 7 auralite control communication cable access is via the fitted cable gland s which are suitable for Ø3 6mm cable 8 auralite Communication Cable Unshielded 4 Core 18 24AWG Stranded Tin...

Страница 18: ...18 auralite Wiring Diagrams 0V 12V A B auralite connection at Indicator auralite connection at Unit 0V 12V A B ...

Страница 19: ... EE 141 Volt free boost switching of MVHR controller PCB using single pole switches TP 502 TP 503 TP 507 and or TP500 TP501 humidistat There is no limit to the number of single pole switches or humidistats that can used TP500 TP501 Humidistat 1 2 3 Boost switching and Humidistat connection ...

Страница 20: ...Three position rotary switch Setback Mode switching and connection Volt free setback switching of MVHR controller PCB using single pole latching switch and or volt free normally open relay contacts To avoid the unit being inadvertently left in Setback Mode it is recom mended that only one latching switch is fitted Volt free setback switch or normally open relay contacts V u N o ...

Страница 21: ...21 Wiring Diagrams ...

Страница 22: ...22 Notes ...

Страница 23: ...ed potentiometers to maximum or reset the controller Control Parameters The Boost Speed cannot be set lower than the Continuous Speed The Continuous Speed cannot be set higher than the Boost Speed All switching inputs are disabled when the Program Run Switch is in Continuous or Boost positions Speed control potentiometers are disabled when the Program Run switch is in centre Run position Boost Ove...

Страница 24: ...ing Boost Supply Extract Speeds 1 Move Program Run Switch to Boost position 2 Rotate supply fan Boost Speed adjustment potentiometer to achieve required supply boost air flow 3 Rotate extract fan Boost Speed adjustment potentiometer to achieve required extract boost air flow 4 Return Program Run Switch to centre position to exit commissioning Boost Overrun Boost Overrun Timer is variable between 0...

Страница 25: ...m the Continuous position to the Boost position and back to the Run position To ensure that the reset switch movements are registered by the controller wait two seconds between each switch movement Controller reset is now complete Hardware Reset Certain conditions repeated supply interruptions etc can activate the automatic motor protection mode Whereby the fan motors are prevented from operating ...

Страница 26: ...ite Indicator Panel will display a filter notification after 6 months of use If filter maintenance is being done less frequently the notification can be reset Replacement Filters are available from Titon Titon HRV Q Plus Filters are available in two grades G3 and G4 Filter media should be replaced like for like Filter Part numbers in table below The Unit part number can be found on the serial numb...

Страница 27: ... into the right hand opening and in the correct orientation see illustration 5 Replace Filters by carefully sliding the replacement cleaned filters 6 Replace the Filter Covers Do not overtighten screws auralite Filter Notification Reset Ensure the HRV is powered up To clear the auralite filter notification press hold the reset switch with a ball point pen or similar object for 10 second The switch...

Страница 28: ...r replacement is the reverse of the above steps Ensure it is securely located at the top before tightening screws Cleaning Interior For best results 1 Slide out Filter Frames fitted either side of heat exchanger 2 Carefully remove any dust from face of heat exchanger interior of the unit and the Bypass if fitted using a vacuum cleaner 3 Do not use water or any other fluids Cleaning Exterior For be...

Страница 29: ...29 Condensate Tray If the Condensate Tray is split a replacement must be ordered and fitted HRV 1 25 Q Plus Part No XP40042 012 HRV1 75 2 3 Q Plus Part No XP40142 012 Condensate Tray ...

Страница 30: ...30 Service Record Serviced By Company Date Notes ...

Страница 31: ...31 Serviced By Company Date Notes ...

Страница 32: ...iton co uk Web www titon com DO 5168 issue 04 2013 TITON In the event of any queries please contact the system installer Ensure this booklet is passed to the householder once installation and commissioning of the ventilation system is complete This Product Manual must be kept in the Home Information Pack and used as a service record Installed by ...