Wiring & Safety
WARNING: The unit MUST be earthed. All wiring must conform to current I.E.E.
Wiring Regulations and all applicable standards and Building Regulations.
1. Electrical installation of the appliance MUST be carried out by a suitably
qualified competent person.
2. The unit is supplied with a mains rated 3 core flexible cord (PVC sheathed,
brown, blue and green/yellow 0.75mm²).
3. Inspect the appliance and electrical supply cord. If the supply cord is damaged,
it must be replaced by the manufacturer, their service agent or similarly
qualified persons in order to avoid a hazard.
4. The appliance must be connected to a local double pole isolation switch with a
contact separation of at least 3mm.
5. HRV1.25
Q Plus
, HRV1.75
Q Plus
, & HRV2
Q Plus
are suitable for 230V ~ 50/60Hz
single phase with a fuse rating of 3A.
6. HRV3
Q Plus
suitable for 230V ~ 50/60Hz single phase with a fuse rating of 5A.
7.
auralite
®, control & communication cable access is via the fitted cable gland(s)
which are suitable for Ø3- 6mm cable.
8.
auralite
® Communication Cable - Unshielded 4 Core 18-24AWG Stranded,
Tinned Copper.
9. Communication cable should not be placed within 50mm or on the same
metal cable tray as 230V switched live, lighting or power cables and any cables
not intended for use with a HRV.
10. Ensure all cable glands are fully tightened.
Wiring Connections Access
Access to the connections for
auralite
®, Boost and other volt free control functions
is via the hinged cover on the top of the unit, at the front. For access for service and
maintainance remove the whole cover.