K-Box A6 User's Manual
English
8 / 44
tiko Energy Solutions AG
IM-0005-0001 Rev. 8
Specifications
Device Characteristics
Product Number
01.9006
CK-01.9006-P3
Input / Output Voltage
3 x 230/400 VAC
Input / Output Current
max. 65 A
Input / Output Wire Specification*
2.5 mm²
–
25 mm² (AWG 4 ~ 14)
Relay Switching Voltage
100 V
–
240 V
Relay Switching Current
max. 10 A
Relay Wire Specifications
0.14 mm²
–
1.5 mm² (AWG 16 ~ 26)
Frequency
50 Hz
Voltage of breaker before K-Box
max. 420 V (3 phases)
Current of breaker before K-Box
max. 65 A
Min. Measurable Current
± 0.1 A
Max. Measurable Current
± 65 A
Measurement Tolerance
± 1% @ 1 A
–
65 A
User Interface
2 push buttons, 2 LEDs (green)
Connectivity
PLC HomePlug GreenPHY
Dimensions
106 x 92 x 70 mm
Weight
430 g
Max. Power Consumption
Relay activated: less than 2 W
Relay deactivated: less than 1.5 W
* A wire cross-section of 1.5 mm² / AWG 16 may be used as long as an appropriate boot-
lace ferrule is properly crimped onto the wire.
Operating Conditions
Storage Conditions
Temperature (min.)
-10 °C
-20 °C
Temperature (max.)
+55 °C
+70 °C
Relative Humidity
10% - 85%
no condensation
5% - 95%
no condensation
Maximum Altitude
2000 m
-