K-Box A6 User's Manual
English
7 / 44
tiko Energy Solutions AG
IM-0005-0001 Rev. 8
Uninstalling
External voltage risk! An external voltage source can be connected to the
K-Box relay terminals. Even if all the main counters are open/disconnected,
there could still be high voltage on the relay terminal clamps coming from
an auxiliary source (e.g. ripple control, UPS, generator, PV, emergency
PSU). Before any handling verify that there is no voltage source wired to
the K-Box.
Step 1
Remove power from the electrical panel.
Step 2
Remove power from any auxiliary circuit (e.g. ripple control, UPS, gen-
erator, PV, emergency PSU).
Step 3
Verify that there is no tension on the K-Box clamps.
Step 4
Remove the cover panel. Unwire and remove the device.
Step 5
Put the cover panel back. Ensure that no electrical contact can be
touched.
Step 6
Power on the system.
Step 7
If the device remains property of
tiko Energy Solutions AG
or
its authorized reseller, it must be returned. Otherwise, the
ultimate disposal of a device shall be handled according to
national laws and regulations.