44
normal operational state.
3.7 4-way valve fault protection
Judgment based on the entire process when the unit runs in heating mode (after 4-way
valve is connected to power);
When THo2
average
(IDU in operation)
≤
-10°C for 3 minutes or THo2
average
(IDU in operation)
≤
5°C for 10 minutes, the unit will automatically turn off and send alarms of abnormal
4-way valve; the unit will restart after 3 minutes. If error is reported 3 times in 2 hours, the
unit automatically turns off to prevent damages.
Whole-process protection available for any unit in defrosting mode or oil return process
during heating mode.
Heating mode:
When pressure difference within a module < 5 Bar for 10 minutes (timing starts after
switched to 4-way valve), insufficient pressure difference alarm will be triggered:
When pressure difference > 5 Bar or error lasts for 5 minutes, fault is cleared; if error lasts
for 10 minutes, the system enters standby mode.
Cooling mode:
When pressure difference within a module < 5 Bar for 10 minutes (timing starts after the
platform operates), insufficient pressure difference alarm will be triggered:
When pressure difference > 5 Bar or error lasts for 5 minutes, fault is cleared; after
10 minutes, the system recovers to normal operation.
3.8 Anti-cold-air control
Содержание P70131000000
Страница 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Страница 16: ...16 1 5 TIMS080 100 120AST Copper silencer 1 6 TIMS140 160 180AST Copper silencer Refrigerant cooling loop ...
Страница 38: ...38 Heating mode ...
Страница 46: ...46 4 1 Remote controller instructions Functions ...
Страница 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Страница 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Страница 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Страница 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Страница 131: ...131 2 Low voltage is too low ...
Страница 149: ...149 ...
Страница 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Страница 151: ...151 2 23 Trip ...
Страница 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...