2.17 IDU forms condensation or leaks
IDU forms condensation or
leaks
Check leak source (generally condensate water or
condensation); condensation deposits at air outlet or panel,
and condensate water results from drain pump or
condensing water pipe.
Condensate water
Check whether connecting-terminal signal output of water
level switch on PCB is correct Whether drain pump works
properly
Whether lift height of condensate water is within specified range
Whether drainage outlet is blocked Whether condensing water
pipe is tilted properly (1/100) Whether pipe joints and throttle
components are properly insulated
Whether main drainage pipe is blocked (if yes, how many IDUs
leak) Whether main condensing water pipe is provided with air
outlet
Condensation Whether air outlet is obstructed Whether air flow is
small Whether indoor humidity is high Whether fan
stops but EXV doesn’t (due to non-uniform power
supply to IDUs)
Fault exists
Replace IDU PCB board or drain pump
Make modifications in accordance with the
technical manual
Fault exists
OK
OK
Содержание P70131000000
Страница 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Страница 16: ...16 1 5 TIMS080 100 120AST Copper silencer 1 6 TIMS140 160 180AST Copper silencer Refrigerant cooling loop ...
Страница 38: ...38 Heating mode ...
Страница 46: ...46 4 1 Remote controller instructions Functions ...
Страница 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Страница 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Страница 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Страница 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Страница 131: ...131 2 Low voltage is too low ...
Страница 149: ...149 ...
Страница 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Страница 151: ...151 2 23 Trip ...
Страница 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...