133
Fault identification conditions: the unit starts fault protection and fails to turn on
properly. The unit must be restarted after power off.
Possible causes:
①
Abnormal main board
②
Refer to relevant handling methods
Troubleshooting:
2.16 Phase sequence (default phase) fault
Code displayed:
ODU main board displays E023 (applicable to AA/AS/AX models).
Fault detection method:
Check whether the unit’s input power cord is not connected or
wrongly connected.
Fault identification conditions: ODU main board sends a false alarm and the unit
fails to work properly
Possible causes:
①
The unit’s input power cord is not connected
②
The unit’s input power cord sequence is not consistent with the connecting terminal
sequence
Содержание P70131000000
Страница 15: ...15 1 3 TIMS080 100 120 140 160AX 1 4 TIMS180 200 220AX ...
Страница 16: ...16 1 5 TIMS080 100 120AST Copper silencer 1 6 TIMS140 160 180AST Copper silencer Refrigerant cooling loop ...
Страница 38: ...38 Heating mode ...
Страница 46: ...46 4 1 Remote controller instructions Functions ...
Страница 65: ...65 Then the following screen appears Click IDU Data set IDU operating data click Confirm ...
Страница 66: ...66 3 Centralized Control 3 1 Methods of installing TIMS centralized wired controller ...
Страница 103: ...103 Troubleshooting Remarks Figure 1 Thermal conductive silicon grease is applied unevenly ...
Страница 108: ...108 Troubleshooting Measure the in between pressure DC Body Electrical wiring drawing ...
Страница 131: ...131 2 Low voltage is too low ...
Страница 149: ...149 ...
Страница 150: ...150 2 22 Compressor startup current is too large Fault code E007 E03 4 ...
Страница 151: ...151 2 23 Trip ...
Страница 162: ...162 2 2 IDU TMDN AB AC TMDH A TMDF A TMDN AB EXV 220V 50Hz Water level On Off ...