21
DMC3S - Manual - 08 - 2021
Inverse time
[1]
Second inverse time threshold (
I
PD
>>
inv
) 0.050...20.0
I
n
0.050...0.995
I
n
(step 0.005
I
n
)
1.00...20.00
I
n
(step 0.01
I
n
)
Characteristic angle (
Theta
PD
>>
inv
)
0...359°
(step 1°)
Operating time (
t
PD
>>
inv
) 0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
Threshold I
PD
>>>
Reset delay
I
PD
>>>
(
t
PD
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Third definite time threshold (
I
PD
>>>
def
)
0.050...25.0
I
n
0.050...0.995
I
n
(step 0.005
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...25.0
I
n
(step 0.1
I
n
)
Characteristic angle (
Theta
PD
>>>
def
)
0...359°
(step 1°)
Operating time (
t
PD
>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rPD
>>>
def
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIPD
>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink activation time (
t
atcIPD
>>>
def
)
1...60 s (step 1 s)
Threshold I
PD
>>>>
Type of characteristic
(
I
PD
>>>>
Curve)
DEFINITE,
IEC/BS A, B, C, B-LI
Reset delay
I
PD
>>>>
(
t
PD
>>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Fourth definite time threshold (
I
PD
>>
def
)
0.050...25.0
I
n
0.050...0.995
I
n
(step 0.005
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...25.0
I
n
(step 0.1
I
n
)
Characteristic angle (
Theta
PD
>>>>
def
)
0...359°
(step 1°)
Operating time (
t
PD
>>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rPD
>>>>
def
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIPD
>>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink activation time (
t
atcIPD
>>>>
def
)
1...60 s (step 1 s)
Note1
Inverse time curve IEC 255-3/BS142 (type A or SIT):
t = 0.14 · t
PD
>
inv
/ [(I/I
PD
>
inv
)
0.02
- 1]
Very inverse time curve IEC 255-3/BS142 (type B or VIT):
t = 13.5 · t>
inv
/ [(I/I
PD
>
inv
) - 1]
Long inverse time curve (IEC 255-3/BS B LTI):
t = 120 · t>
inv
/ [(I/I
PD
>
inv
) - 1]
Extremely inverse time curve IEC 255-3/BS142 (type C or EIT):
t = 80 · t
PD
>
inv
/ [(I/I
PD
>
inv
)
2
- 1]
t
:
operating time
t
PD
>
inv
:
operating time regulation
I
PD
>
inv
:
trip threshold regulation
I
PD
:
measured current
Asymptotic reference value:
1.1
I
PD
>
inv
Minimum operating time:
0.1
s
Dynamic: 1.1 ≤ I/I
PD
>
inv
≤ 20
With regulation I
PD
>
inv
greater than
2.5
I
n
, the upper limit of the measurement range is
30
I
n
Содержание DMC3S
Страница 76: ...76 DMC3S Manual 08 2021 EACx fxa dfx dt fxb Ueac EnUeac Ueac EnUeac ULS EnULS UG EnUG UDT EnUDT P EnP EAC Logic...
Страница 105: ...105 DMC3S Manual 08 2021 DMC3S DIMENSIONS front internal and rear views...
Страница 106: ...106 DMC3S Manual 08 2021 DMC3S DIMENSIONS viewed from above...
Страница 107: ...107 DMC3S Manual 08 2021 DMC3S DIMENSIONS DMRIS0 module...