74
DMC3S - Manual - 08 - 2021
—
Logical block - Block1
To block the trip of a given protection function, one can map to the logical block function to the
logical inputs.
[1]
The logical inputs are mapped in the menu
Set \ Input board inputs \ Input IN1-1 (Input IN1-6)
; select
Logical block
for the parameter
Input function IN1-x
(x=1...6)
All protection functions for which the logical block is enabled are blocked when the signal is active.
The status of the function's logical block is available in read (ThySetter and comms interfaces); it is
active when the following conditions obtain simultaneously:
• Logical input activated,
• Start of function active (ON),
• Trip of function in standby (OFF).
The logical block is not subject to inhibition criteria after a programmable delay, hence the associat-
ed protection function is block for as long as the input remains active.
[2]
Note 2 The block signal holds the timer in reset
Blocco_L.ai
RESET
Operate time
0
T
Measure
Input
TR
IP
PI
NG M
AT
RI
X
(LE
D+R
EL
AY
S)
BLK1xx
Operate time
Threshold
Startxx
Startxx
Tripxx
Tripxx
&
&
Enable (ON
≡
Enable)
Block1 input (ON
≡
Block)
Block1 info (internal state)
xxBLK1
Block1
Block1
Binary input IN1-x (x=1...6)
T
0
Logic
IN1-x
t
ON
IN1-x
t
ON
IN1-x
t
OFF
T
0
n.o.
n.c.
IN1-x
t
OFF
&
Protection threshold xx enabled to receive logical block
Functional diagram of logical block - Block1
Start
Block1 (input)
Block1 (output)
Trip
Operate time
t
Timers-Block1.ai
Logical block timers (Block1)
CAUTION
The activation of a logical input to which the logical block has been mapped blocks all protections
for which the block is enabled
Содержание DMC3S
Страница 76: ...76 DMC3S Manual 08 2021 EACx fxa dfx dt fxb Ueac EnUeac Ueac EnUeac ULS EnULS UG EnUG UDT EnUDT P EnP EAC Logic...
Страница 105: ...105 DMC3S Manual 08 2021 DMC3S DIMENSIONS front internal and rear views...
Страница 106: ...106 DMC3S Manual 08 2021 DMC3S DIMENSIONS viewed from above...
Страница 107: ...107 DMC3S Manual 08 2021 DMC3S DIMENSIONS DMRIS0 module...