24
DMC3S - Manual - 08 - 2021
Threshold I
ED
>>>
Reset delay (
t
ED
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Fourth definite time threshold (
I
ED
>>>
def
-
U
ED
>>>
def
)
Residual current operating time
0.005...25.0
I
En
0.005...0.995
I
En
(step 0.005
I
En
)
1.00...9.99
I
En
(step 0.01
I
En
)
10.0...25.0
I
En
(step 0.1
I
En
)
Residual current trip value
0.001...1.000
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Operating
half-sector
1...180°
(step 1°)
Operating time (
t
ED
>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rED
>>>
def
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIED
>>>
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink activation time (
t
atcIED
>>>
def
)
1...60 s (step 1 s)
Threshold 67N.Sb
Reset delay (
t
ED
>>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Fifth 67N definite time threshold (
I
ED
Sb
def
-
U
ED
Sb
def
)
Residual current operating time
0.005...25.0
I
En
0.005...0.995
I
En
(step 0.005
I
En
)
1.00...9.99
I
En
(step 0.01
I
En
)
10.0...25.0
I
En
(step 0.1
I
En
)
Residual current trip value
0.001...1.000
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Operating
half-sector
1...180°
(step 1°)
Operating time (
t
EDSbdef
) 0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rED
Sb
def
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIED
Sb
def
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink activation time (
t
atcIED
Sb
def
)
1...60 s (step 1 s)
Threshold I
ED
>>>> (Intermittent faults)
Residual current trip value
0.040...1.500
U
En
(step 0.001
U
En
)
59N startup drop-out delay (
t
ED
>>>>
RRI59N
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
67N startup drop-out delay (
t
ED
>>>>
RRI67N
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Operating time (
t
ED
>>>
def
)
0.50...60.0
s
0.50...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
Maximum fault time for disable (
t
ED
>>>>
Inb
)
0.50...2.00 s (step 0.01 s)
Disable hold time (
t
ED
>>>>
1s
)
0.50...2.00 s (step 0.01 s)
Threshold I
ED
>>>> (Evolving faults)
Control threshold
U
E
> (
I
ED
>>>>>-
U
E
>)
0.040...1.500
U
En
(step 0.001
U
En
)
59N startup drop-out delay (
t
ED
>>>>>
RRIC
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Observation activation delay (
t
ED
>>>>>
RAO
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Observation time (
t
ED
>>>>>
o
)
0.50...2.00 s (step 0.01 s)
Содержание DMC3S
Страница 76: ...76 DMC3S Manual 08 2021 EACx fxa dfx dt fxb Ueac EnUeac Ueac EnUeac ULS EnULS UG EnUG UDT EnUDT P EnP EAC Logic...
Страница 105: ...105 DMC3S Manual 08 2021 DMC3S DIMENSIONS front internal and rear views...
Страница 106: ...106 DMC3S Manual 08 2021 DMC3S DIMENSIONS viewed from above...
Страница 107: ...107 DMC3S Manual 08 2021 DMC3S DIMENSIONS DMRIS0 module...