3.5 Switching Outputs
Use enclosed counter plug for electrical connection. Connect
only when power is off.
Maximum load for the relays is 2 A / 40 VDC or 3 A / 250 VAC.
Phoenix Combicon, 16pin
The contacts are shown in
state-of-rest position, i.e.
switching function "off"
For process control this output of the VD10 provides switching functions by
means of 8 relay switches (closer) SP1 to SP8. The switching outputs can be
assigned to measuring channels 1 to 4 or function keys F1 or F2 (s. chapter 4.4).
3.6 USB Interface
1:
2:
3:
4:
5:
Mini socket, type B
VCC, +5V
Data –
Data +
GND
GND
The USB-interface can be connected to a PC, e.g. for documentation of
measurements in combination with Windows-Software VacuGraph