APPENDIX “A”
THOMSON POWER SYSTEMS
©
TYPICAL TS 870 ATS
COMMISSIONING PROCEDURES
(S-Style 100A-800A)
9087A - 198th Street, Langley, BC, Canada V1M 3B1 · Telephone (604) 888-0110
Email: [email protected] · www.thomsonps.com
11. Verify the status of the following indicator lights on the TSC 900 Display Home page:
- Utility Source Green light is On
- Load on Utility Green light is On
12. Run the generator manually and confirm generator voltage on the TSC 900 DISPLAY Home page is
displaying the correct voltage to match the rating of the ATS.
13. With generator still running, confirm generator phasing matches that of the Utility supply by viewing
the Utility and Generator metering pages with phase rotation indication on the TSC 900 DISPLAY. If
phase rotation does not match, de-energize ATS and re-confirm supply rotation and power wiring is
correct.
14. Verify the TSC 900 DISPLAY Home Page Generator Source Red Light is On
15. Manually stop generator and place the generator controls in the Automatic position.
16. To confirm automatic starting and load transferring of the generator, press the Change Mode control
button on the TSC 900 DISPLAY home page and select On Load Test mode. The generator will start
Содержание TS 870
Страница 2: ......
Страница 12: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 10 Thomson Power Systems ...
Страница 13: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 11 Thomson Power Systems ...
Страница 34: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 32 Thomson Power Systems ...
Страница 63: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 61 Thomson Power Systems 18 NOTES ...
Страница 74: ......
Страница 76: ......