T-STYLE ATS -MANUAL OPERATION
The transfer switch maybe operated manually for maintenance or emergency operation
conditions provided both Utility and Generator supplies are de-energized prior to manual
operation.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be serviced only by qualified electrical personnel utilizing safe
work practices and appropriate Personal Protective Equipment (PPE).
Many components of this equipment operate at line voltage.
DO NOT TOUCH. Use only electrically isolated tools.
Install and close all covers before applying power to this equipment
Do not open covers to equipment until ALL power sources are disconnected
Failure to do so may cause personal injury or death
Once both Utility and Generator supplies are de-energized the following procedure can be
used to operate the Transfer Switch manually.
1. Disconnect the ATS Power Chassis & Voltage Sensing Isolation Plugs (PL12 & PL15)
to prevent automatic operation.
2. Open ATS enclosure door and locate Manual Operation Handle knob (see photo
below).
Manual Operation
Handle Knob
Содержание TS 870
Страница 2: ......
Страница 12: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 10 Thomson Power Systems ...
Страница 13: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 11 Thomson Power Systems ...
Страница 34: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 32 Thomson Power Systems ...
Страница 63: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 61 Thomson Power Systems 18 NOTES ...
Страница 74: ......
Страница 76: ......