TS 870 Transfer Switch
PM062 REV 11 16/04/19
57
Thomson Power Systems
Generator does not start or stop
when it should
Remote engine control panel is not set to
automatic mode
Verify remote engine control panel is set for automatic
operation
Engine start contact is wired incorrectly
from ATS to engine control panel
Verify engine start contact is wired correctly from ATS
to engine control panel
Incorrect TSC 900 Engine start contact is
used
For single engine applications, use Engine Start
Signal #2 contact on TSC 900 lower terminal block
(J10b)
TSC 900 Engine start contact terminal
block (j10b) is unplugged
Verify 2 position TSC 900 terminal block j10b is fully
inserted into controller and it is connected to correct
position (i.e. lower TB)
Defective TSC 900 SCU Engine Start
relay/contact
•
Verify Engine start signal LED diagnostic light is
illuminated on SCU when engine is signaled to
start. If LED is on, verify contacts are closing.
If defective Return TSC 900 SCU to Thomson Power
Systems using RMA process
Engine Start and/or Cooldown timers may
be duplicated in both ATS control and
Engine control Panel
Disable timers in either ATS or Engine control panel.
No time delay when there should
be
Incorrect TSC 900 time delay setting
Verify TSC 900 timer setting
Power is not available at the load
terminals but the utility or
generator power switching
device appears to be closed to a
live source
Utility or Generator power switching device
has tripped open due to an over current
condition.
Power Switching device must be reset by manually
operating the ATS mechanism to the other source,
then back to the source which was tripped.
Mechanism has failed to operate the power
switching device toggle far enough to close
the power switching unit.
Limit switch failure or improper adjustment. Contact
Thomson Power system for adjustment procedure of
limit switch
The transfer switch has
completed a transfer, but the
motor has overheated and the
internal thermal protector has
opened
Limit switch failure or improper adjustment
Contact Thomson Power system for adjustment
procedure or replacement of limit switch
GHC Display is not showing any
system information
GHC screen may be in a “sleep” mode.
Touch screen to re-activate LCD display
GHC USB cable is unplugged at the GHC
end or the SCU end
Verify USB cable is fully inserted into the GHC and
SCU devices
Содержание TS 870
Страница 2: ......
Страница 12: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 10 Thomson Power Systems ...
Страница 13: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 11 Thomson Power Systems ...
Страница 34: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 32 Thomson Power Systems ...
Страница 63: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 61 Thomson Power Systems 18 NOTES ...
Страница 74: ......
Страница 76: ......