TS 870 Transfer Switch
PM062 REV 11 16/04/19
41
Thomson Power Systems
switching device. Refer to Diagrams #1 & #2 below. Verify the
generator power switching device contacts are closed via Red (I)
Closed contact status flag.
NOTE:
If the Transfer Switch is supplied with Closed
Transition Transfer feature, the mechanical close
push button on the face of the power switching
unit is not available for use. A separate electrical
close push button located on the power switching
unit door is provided for manual closing. Power
switching unit closure is only permitted in open
transition mode (i.e. Utility power switching device
must be open)