MEC 2 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM056 Rev 6 05/10/15
Thomson Technology
77
ANALOG FAULT PROGRAMMING MENU
FAULT
NAME
INPUT ANALOG
TYPE
FAULT
E=ENABLE
D=DISABLE
SETPOINT
LEVEL
(PICK-UP)
SETPOINT
LEVEL
(DROP-OUT)
ACTION
S=SHUTDOWN
A=ALARM
ALARM LATCH
Y=YES
N=NO
BYPASS ON
START
Y=YES
N=NO
TRANSIENT
DELAY (SEC)
LOW OIL
PRESS#1
ALARM
PRESS
SENDER
E
*
30PSI N/A A
Y
Y
*
2.0
LOW OIL
PRESS#2
SHUTDOWN
PRESS
SENDER
E
*
20PSI N/A S
Y
Y
*
2.0
* Indicates feature is non-programmable (i.e. is fixed) in software
11.2. DIGITAL FAULT PROGRAMMING MENU
TYPICAL PROGRAM FACTORY DEFAULT SETTINGS
DIGITAL FAULT PROGRAMMING MENU
FAULT
NAME
INPUT #
ACTION
S=SHUTDOWN
A=ALARM
ALARM
LATCH
Y=YES
N=NO
POLARITY
O=OPEN
C=CLOSE
BYPASS ON
START
Y=YES
N=NO
TRANSIENT
DELAY
(SEC)
LOW OIL
PRESSURE
1 S __ O Y 0.5
HIGH ENG
TEMP
2 S __ O Y 1.0
BATT CHGR
INPUT FAIL
3 A Y C N
30.0
LOW FUEL
LEVEL
4 A N C N 0.1
11.3. CALIBRATION MENU
CALIBRATION MENU
VOLTS A-B
ZERO XXX XXXVAC
VOLTS
A-B
SPAN XXX XXXVAC
VOLTS B-C
ZERO XXX XXXVAC