![THOMSON MEC 2 Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/thomson/mec-2/mec-2_service-manual_1108984081.webp)
MEC 2 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM056 Rev 6 05/10/15
Thomson Technology
76
MAIN PROGRAMMING MENU
PROG OUTPUT #6
WARMUP DELAY
0 – 99 SECONDS
NEUTRAL DELAY
0 – 99 SECONDS
RETURN DELAY
0 – 999 SECONDS
RESET RUN HOURS
ACCESS VIA MASTER PASSWORD ONLY
YES/NO
TOGGLE
YES/NO,
11.1. ANALOG FAULT PROGRAMMING MENU
TYPICAL PROGRAM FACTORY DEFAULT SETTINGS
ANALOG FAULT PROGRAMMING MENU
FAULT
NAME
INPUT ANALOG
TYPE
FAULT
E=ENABLE
D=DISABLE
SETPOINT
LEVEL
(PICK-UP)
SETPOINT
LEVEL
(DROP-OUT)
ACTION
S=SHUTDOWN
A=ALARM
ALARM LATCH
Y=YES
N=NO
BYPASS ON
START
Y=YES
N=NO
TRANSIENT
DELAY (SEC)
UNDER
VOLTAGE
AC VOLTAGE
E
*
S
Y
Y
*
5.0
OVER
VOLTAGE
AC VOLTAGE
E
*
S
Y
N
2.0
UNDER
FREQUENCY
AC
FREQUENCY
E
*
S
Y
Y
*
5.0
OVER
FREQUENCY
AC
FREQUENCY
E
*
A
Y
N
2.0
OVER
CURRENT
AC
CURRENT
E
*
500 4990 A
Y
N 20.0
WEAK
BATTERY
DC
VOLTAGE
E
*
18.0 N/A A
*
Y
N
*
3.0
LOW
BATTERY
VOLTAGE
DC
VOLTAGE
E
*
25.6 N/A A
*
N
N
*
120.0
HIGH
BATTERY
VOLTAGE
DC
VOLTAGE
E
*
30.4 N/A A
*
N
N
*
10.0
LOW
ENGINE
TEMP
TEMP
SENDER
E
*
95
°
F
N/A
A
*
Y
N
*
5.0
HIGH ENG
TEMP #1
ALARM
TEMP
SENDER
E
*
198
°
F
N/A A Y Y 2.0
HIGH ENG
TEMP #2
SHUTDOWN
TEMP
SENDER
E
*
206
°
F
N/A S Y Y 2.0