MEC 2 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM056 Rev 6 05/10/15
Thomson Technology
60
9.4.5. TRANSIENT DELAY TIMES
This allows the selected fault circuit to be inhibited from being activated until the
specified time delay period has expired. Delay times from 0.0 to 999.9 seconds
are available by entering the time required.
9.5. DIGITAL FAULT PROGRAMMING MENU
To program the controller’s digital fault circuits, refer to the following descriptions.
9.5.1. DIGITAL FAULT LABEL
To select the desired fault label description, use the
INCREMENT
key to scroll
through the available labels. The digital fault labels are stored in non-volatile
memory and are as follows:
AIR DAMPER TRIPPED
HIGH OIL TEMP
BAT CHARGER INPUT FAIL
HIGH WINDING TEMP
BAT CHRG TROUBLE
LOW COOLANT LEVEL
BREAKER TRIPPED
LOW ENGINE TEMP
DC FAIL
LOW FUEL LEVEL
FAILED TO SYNC
LOW FUEL PRESS
GEN BREAKER OPEN
LOW OIL LEVEL
GROUND FAULT
LOW OIL PRESSURE
HIGH BEARING TEMP
REMOTE EMERG.STOP
HIGH COOLER VIBRATION
REVERSE POWER
HIGH ENGINE TEMP
BASIN RUPTURE
HIGH ENGINE VIBRATION
ATS IN BYPASS
HIGH FUEL LEVEL
FUEL LEAK
HIGH OIL LEVEL
LOW FUEL PRESS
NO LOAD TEST
BAT CHARGER FAIL
*HIGHINTKMANFTEMP
VENT DAMPER FAIL
HIGH FUEL LEVEL
FAIL TO SYNC
“Blank” (i.e. no text for unused inputs)
Once the desired fault label is selected, press the
ENTER
key to accept the
selection.