18 Operating
Status
18.1
UPS Mode (OFF line UPS)
In this mode, the output of inverter has grid/mains priority. In case of grid/mains failure, the AC-Output switches to
inverter power. Switch over time is less than 6ms.
If grid/mains power is back within tolerance the load is switched back to grid/mains power.
UPS Mode
Inverter OK
Grid OK
Inverter OK
Grid failure
Inverter failure
Grid OK
ONLINE LED
1
0
1
BYPASS LED
0
0
1
UPS MODE LED
1
0
1
INV MODE LED
0
0
0
BACKUP LED
0
1
0
INV FAIL LED
0
0
1
Load Connect to
Grid
Inverter
Grid
Alarm Contact
Com - Nc
Com - On
Com - Nc
18.2
Inverter Mode (Online UPS)
This mode is usually in use, when grid is very unstable or if a very high quality AC-source is required for sensitive
equipment. To operate the system in this mode it requires to charge the batteries all the time in order to have
enough power available.
In this mode, the load is connected to inverter. In case of inverter failure (low battery, overload, etc.), the AC-
Output switches to grid/mains power. Switch over time is less than 6ms.
If inverter is operating again the load is switched back to inverter power.
INV Mode
Inverter OK
Grid OK
Inverter OK
Grid failure
Inverter failure
Grid OK
ONLINE LED
1
0
1
BYPASS LED
0
0
1
UPS MODE LED
0
0
0
INV MODE LED
1
1
1
BACKUP LED
1
1
1
INV FAIL LED
0
0
1
Load Connect to
Inverter
Inverter
Grid
Alarm Contact
Com - Nc
Com - On
Com - Nc
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK