Manual UPSW.doc
11/15
Version 2.11.14
17.7
Over voltage protection indicator: (OVP)
The over voltage indicator indicates that the power inverter has shut itself down because its input voltage exceed-
ed the maximum input voltage.
17.8
Under voltage protection indicator: (UVP)
The under voltage indicator indicates that the power inverter has shut itself down because its input voltage fell
below minimum input voltage.
17.9
Over temp protection indicator: (OTP)
The over temp indicator indicates that the power inverter has shut itself down because its temp has become over-
heated. The power inverter may overheat because it has been operated at power levels above its rating, or be-
cause it has been installed in a location which does not allow it to dissipate heat properly. The power inverter will
automatically back up, once it has cooled off.
17.10 Overload protection indicator: (OLP)
The overload indicator indicates that the power inverter has shut down. A manual reset is necessary (switch it
OFF and ON again) to restart operation. This is a safety function to protect your battery when the inverter oper-
ates in a remote area.
Model
DC Input over volt-
age shutdown
DC Input over volt-
age alarm
DC Input under
voltage alarm
DC Input under
voltage shutdown
UPSW2000/3000 12V
16.0 VDC
15.5 VDC
10.5 VDC
10.0 VDC
UPSW2000/3000 24V
32.0 VDC
31.0 VDC
21.0 VDC
20.0 VDC
UPSW2000/3000 48V
62.0 VDC
61.0 VDC
43.0 VDC
42.0 VDC
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK