A repeated check of the through-flow switch is activated whenever it does not switch within 15 sec after the 
pump started to operate. The pump halts and when another 45 passes, another attempt to start the boiler is made. 
This is repeated ten times. If the tenth try is not succesfuls, it is necessary to switch the boiler off and switch it 
on subsequently by the mode switch. If the non-operation state of the pump between the halt and the repeated 
start of the boiler lasts longer than 30 min, the first operation interval of the pump is prolonged at 180 sec. The 
intervals between the individual test cycles are indicated according to the following list of malfunctions. 

 

An accredited service technician is bound to inform the user about the correct use of the boiler, about its 

parts and safety elements, to fill in the letter of guaranty and to give the user this manual.  
The user has to use the boiler only in the ways described in this manual. This is also the condition for 
guarantee. The user is strictly forbidden to change or interfere with the fixed parts of the boiler!

  

 
 

8. SIT 848 SIGMA GAS FITTING 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

      gas inlet

 

    solenoid coils 

module for measuring 
the inlet gas pressure

 

gas outlet

setting of the air/gas ratio 

air pressure signal inlet

module for measuring 
the outlet gas pressure

 

setting of the starting point of regulation

 
 

SIT 848 SIGMA is a gas fitting with proportional regulation: air/gas. It is equipped with two solenoid valves that 
prevent the penetration of gas at the time when the boiler is out of operation. The regulation system works in 
correlation with the feedback signal of the gas pressure from the mixer. Apart from the lockable measuring 
modules

 

of the inlet, outlet and medial gas pressure, there are devices that make it possible to set the correct air-gas 

ratio throughout the output regulation range. 
 
 

1.

 

Starting point of the regulation – setting: 

The setting is done by means of a screw that is placed at the pad of the 
regulation system of the auxiliary membrane. The screw is only accessible if a 
brass cover is removed. 
The air-gas ratio is set at the minimum output of the boiler (i.e. at the minimum 
running speed of the ventilator.) If the screw is screwed in, the proportion of 
gas in the mixture gets lower. 

 

 

2.

 

The air/gas ratio – setting: 

The setting is done by the regulation screw of the gas throttle placed at the 
gas valve outlet. 
 
The air-gas ratio is set at the maximum output of the boiler (i.e. at the 
maximum running speed of the ventilator).  If the screw is screwed in, the 
proportion of gas in the mixture gets lower. 
 

 

 14

 

The solenoid coil connector - wiring diagram: 

Содержание Therm 28 KD

Страница 1: ...Manual for Installation and Maintenance of Condensing Boilers Therm 28 KD KDZ KDC...

Страница 2: ...INSTRUCTIONS FOR OPERATION AND MAINTENANCE 9 OPERATING THE BOILER 9 7 DIMS03 TH01 MODULATION ELECTRONICS 11 8 SIT 848 SIGMA GAS FITTING 14 9 GUARANTEE AND LIABILITY FOR DEFECTS 15 10 GRAPHS OF THE US...

Страница 3: ...ular burner and a modified pipiline conducting the air gas mixture The approriate rationing of the air gas mixture and its mixing is ensured by a mixer and a special gas fitting The latter contains a...

Страница 4: ...perations and the electric circuits participating in the ignition of the burner Important The type of supply of the ionizing current is determined by the neutral It is therefore crucial that the neutr...

Страница 5: ...stem excess pressure bar 0 8 0 8 0 8 Max DHW inlet pressure bar 6 Min DHW inlet pressure bar 0 5 Max heating water outlet temperature o C 80 80 80 Coaxial flue exhaust diameter mm 60 100 60 100 60 100...

Страница 6: ...materials polyurethane polystyrene polyethylene PVC etc Important No flammable objects can be placed closer than at the safe distance from the boiler the minimum distance of the appliance from flamma...

Страница 7: ...by a professional company with valid certification and its professional certified employees and according to the approved documentation for gas fitting The gas regulator is not to be fitted in front...

Страница 8: ...ng system is filled with water the boiler must be unplugged i e the plug must be out of the socket The recommended heating water pressure ranges from 1 to 1 5 bar when the system is cold The heating s...

Страница 9: ...imum Plug the cable into the socket and start the boiler by turning the mode switch Turn the mode switch for a short time to malfunction unblock position so that the boiler gets automatically ignited...

Страница 10: ...ay The meaning of the used symbols temperature failure modes and service data in digital numbers DHW regime DHW temperature displayed heating mode heating temperature displayed boiler burning temperat...

Страница 11: ...l value 6 Offset of the weather compensation curve the numerical value 7 Running speed of the ventilator without a symbol the numerical value x 10 8 Back to the standard indication Once the setting ha...

Страница 12: ...t this moment the burning in the boiler is stopped while the circulation pump is still in operation and the time limit of the repeated ignition is put into operation the service setting of the time li...

Страница 13: ...t the starting power circa 10 sec after the boiler s ignition and increases the boiler output at the maximum level so that the outlet temperature that was previously set by the user can be achieved as...

Страница 14: ...the air gas ratio air pressure signal inlet module for measuring the outlet gas pressure setting of the starting point of regulation SIT 848 SIGMA is a gas fitting with proportional regulation air ga...

Страница 15: ...and maintenance The guarantee covers neither situations caused by non standard conditions in the distribution network voltage fluctuation and overvoltage peaks gas pressure and purity etc nor defects...

Страница 16: ...28 KDC KDZ 0 0 50 0 100 0 150 0 200 0 250 0 300 0 350 0 400 0 450 0 500 0 0 4 0 6 0 8 1 1 2 Water through flow m 3 h Outlet excess pressure mbar Wilo 3 Grunfos 3 Warning The curves of the applicable c...

Страница 17: ...11 Wiring connect of the THERM 28 KD boilers with the DIMS03 TH01 automatics 17...

Страница 18: ...12 Wiring connect of the THERM 28 KDC boilers with the DIMS03 TH01 automatics 18...

Страница 19: ...19 13 Wiring connect of the THERM 28 KDZ boilers with the DIMS03 TH01 automatics...

Страница 20: ...re no 23640 Ventilator MVL 130 24 store no 22141 Ionizing electrode store no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 Expansion vessel 7l store no 22168 Seal pipe store no 23405 Blo...

Страница 21: ...noni condensation device store no 23821 Ignition electrode store no 23640 Ventilator MVL 130 24 store no 22141 Ionising electrode store no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 E...

Страница 22: ...izing electrode strore no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 Expansion vessel 7l store no 22168 Seal pipe store no 23405 Blocking thermostat store no 40035 Transformer 220V 24...

Страница 23: ...17 HANGING THERM 28 KD KDZ KDC BOILERS I 23...

Страница 24: ...sely to each other not further than 50 cm that they are exposed to the same climatic conditions C43 Separated connection to two pipelines within the same shaft The outlet of both shafts is either conc...

Страница 25: ...the requirements of valid norms and regulations The product packaging should be taken to the paper disposal area while the package film should be disposed in the public containers in which the plastic...

Страница 26: ...e authorized person 202 THERM 28 KD THERM 28 KDC THERM 28 KDZ certificate for type testing according to the EC directives for gas appliances 90 396 EEC No E 30 00712 02 THERM 28 KD THERM 28 KDC THERM...

Отзывы: