1.1 Heating mode without weather-compensated regulation 
 
Setting:  
The sensor of outside temperature is not connected, the service switch DS2, DS3 – OFF 
 

The operating state of the boiler starts by the switching of the room thermostat (the mode switch in the winter 

position). In the case of KDC boilers the relay of the three-way valve is activated and the valve is reset into the 
heating position (the starting position of the valve is that of DHW heating, for reasons of time saving). While the 
valve is being reset (circa 8 sec), any efforts to ignite the boiler are blocked. In the case of KD and KDZ boilers the 
starting position of the three-way valve is into the heating, which means that the above mentioned cycle does not 
take place. Then the ventilator is put into operation and the circulation pump and ignition automatics get activated. 
The boiler is ignited at the output that was previously set. The set output is preserved for 2 sec from the ignition of 
the boiler because of the feedback from the ignition automatics. After that the output gets at the minimum level 
with a slow linear rise (circa 1 min) to the point of modulation that is given by the service setting of the maximum 
heating output. The output regulation of the boiler in this phase is categorized as the PID type (referring to its 
proportion/integration/derivation characteristics) while the temperature set by the revolving knob on the control 
panel is maintained in the range of 30 – 80 

o

C. If a system with an input lower than the minimum output of the 

boiler is heated up, the outlet temperature of the heating water exceeds the set value by 5

o

C. At this moment the 

burning in the boiler is stopped, while the circulation pump is still in operation, and the time limit of the repeated 
ignition is put into operation (the service setting of the time limit ranges from 0 to 10 min). Given the vast number 
of consequently regulated heating systems (e.g. zone regulations, thermostatic valves, etc.), the boiler functions as 
an exceedingly adaptable heat source. 

When the room thermostat opens, the pump runs down within a settable time (the factory setting is 0 – 10 

minutes). This function is used to divert the heat from the condensation device and to balance the temperatures of 
different heating elements (useful mainly for horizontal distribution systems) if room thermostats with PI link with 
short operating cycles (e.g. Honeywell CM 27, CM 67) are involved. 

 

1.2 Heating mode with weather compensated regulation 

Setting: Outside sensor connected, service buttons

 

DS2 – ON, DS3 – OFF

 

 

The boiler operates on the same basis as above. The only difference is that the temperature of the heating system 

is controlled automatically, depending on the outside temperature which is detected by the outside sensor. The 
calculation of the necessary temperature of the heating system is a function of the outside temperature and the 

„K“ 

factor (slope of the weather compensation curve). The factor is set by the service technician according to the 

natural environment of the premises and the type of the heating system. Use the adjusting revolving knob on the 
control panel to set the required temperature of the heating system (correction of the offset of the weather-
compensation curve is in the range of 

±

 15 °C). 

The weather compensation curve is calculated for the standard heating system with radiators. 

 

Curve graphs

  

 

          

Slopes of the weather-compensation curve

 

       

Off-sets of the weather-compensation curve

 

 

  

 

 

 

 

 12

 

Содержание Therm 28 KD

Страница 1: ...Manual for Installation and Maintenance of Condensing Boilers Therm 28 KD KDZ KDC...

Страница 2: ...INSTRUCTIONS FOR OPERATION AND MAINTENANCE 9 OPERATING THE BOILER 9 7 DIMS03 TH01 MODULATION ELECTRONICS 11 8 SIT 848 SIGMA GAS FITTING 14 9 GUARANTEE AND LIABILITY FOR DEFECTS 15 10 GRAPHS OF THE US...

Страница 3: ...ular burner and a modified pipiline conducting the air gas mixture The approriate rationing of the air gas mixture and its mixing is ensured by a mixer and a special gas fitting The latter contains a...

Страница 4: ...perations and the electric circuits participating in the ignition of the burner Important The type of supply of the ionizing current is determined by the neutral It is therefore crucial that the neutr...

Страница 5: ...stem excess pressure bar 0 8 0 8 0 8 Max DHW inlet pressure bar 6 Min DHW inlet pressure bar 0 5 Max heating water outlet temperature o C 80 80 80 Coaxial flue exhaust diameter mm 60 100 60 100 60 100...

Страница 6: ...materials polyurethane polystyrene polyethylene PVC etc Important No flammable objects can be placed closer than at the safe distance from the boiler the minimum distance of the appliance from flamma...

Страница 7: ...by a professional company with valid certification and its professional certified employees and according to the approved documentation for gas fitting The gas regulator is not to be fitted in front...

Страница 8: ...ng system is filled with water the boiler must be unplugged i e the plug must be out of the socket The recommended heating water pressure ranges from 1 to 1 5 bar when the system is cold The heating s...

Страница 9: ...imum Plug the cable into the socket and start the boiler by turning the mode switch Turn the mode switch for a short time to malfunction unblock position so that the boiler gets automatically ignited...

Страница 10: ...ay The meaning of the used symbols temperature failure modes and service data in digital numbers DHW regime DHW temperature displayed heating mode heating temperature displayed boiler burning temperat...

Страница 11: ...l value 6 Offset of the weather compensation curve the numerical value 7 Running speed of the ventilator without a symbol the numerical value x 10 8 Back to the standard indication Once the setting ha...

Страница 12: ...t this moment the burning in the boiler is stopped while the circulation pump is still in operation and the time limit of the repeated ignition is put into operation the service setting of the time li...

Страница 13: ...t the starting power circa 10 sec after the boiler s ignition and increases the boiler output at the maximum level so that the outlet temperature that was previously set by the user can be achieved as...

Страница 14: ...the air gas ratio air pressure signal inlet module for measuring the outlet gas pressure setting of the starting point of regulation SIT 848 SIGMA is a gas fitting with proportional regulation air ga...

Страница 15: ...and maintenance The guarantee covers neither situations caused by non standard conditions in the distribution network voltage fluctuation and overvoltage peaks gas pressure and purity etc nor defects...

Страница 16: ...28 KDC KDZ 0 0 50 0 100 0 150 0 200 0 250 0 300 0 350 0 400 0 450 0 500 0 0 4 0 6 0 8 1 1 2 Water through flow m 3 h Outlet excess pressure mbar Wilo 3 Grunfos 3 Warning The curves of the applicable c...

Страница 17: ...11 Wiring connect of the THERM 28 KD boilers with the DIMS03 TH01 automatics 17...

Страница 18: ...12 Wiring connect of the THERM 28 KDC boilers with the DIMS03 TH01 automatics 18...

Страница 19: ...19 13 Wiring connect of the THERM 28 KDZ boilers with the DIMS03 TH01 automatics...

Страница 20: ...re no 23640 Ventilator MVL 130 24 store no 22141 Ionizing electrode store no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 Expansion vessel 7l store no 22168 Seal pipe store no 23405 Blo...

Страница 21: ...noni condensation device store no 23821 Ignition electrode store no 23640 Ventilator MVL 130 24 store no 22141 Ionising electrode store no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 E...

Страница 22: ...izing electrode strore no 20342 Mixer SIT store no 40390 Gas valve SIT store no 40848 Expansion vessel 7l store no 22168 Seal pipe store no 23405 Blocking thermostat store no 40035 Transformer 220V 24...

Страница 23: ...17 HANGING THERM 28 KD KDZ KDC BOILERS I 23...

Страница 24: ...sely to each other not further than 50 cm that they are exposed to the same climatic conditions C43 Separated connection to two pipelines within the same shaft The outlet of both shafts is either conc...

Страница 25: ...the requirements of valid norms and regulations The product packaging should be taken to the paper disposal area while the package film should be disposed in the public containers in which the plastic...

Страница 26: ...e authorized person 202 THERM 28 KD THERM 28 KDC THERM 28 KDZ certificate for type testing according to the EC directives for gas appliances 90 396 EEC No E 30 00712 02 THERM 28 KD THERM 28 KDC THERM...

Отзывы: