background image

Page 5

Section 3.4: Analyzing Component Failure by Conditions

Section 4.0: Adjustments and Repairs
Section 4.1: V1 Mixing Valve Adjustment Instructions with the Unit Running

CONDITION

COMPONENT FAILURE

If the outlet temperature remains above the

normal range for long periods of time

without fluctuation in the outlet temperature.

Follow Section 3.1 & 3.2 to decommission the 

station for repair. Follow Section 4.2 to adjust 

the V1 Mixing Valve outside the unit. If the valve 

cannot be adjusted correctly a replacement WWM 

Diaphragm Actuator is required. If the outlet 

temperature is above 95°F, replacement of the V4 

Control Valve is required. (See section 4.3 &4.4 for 

replacement instructions)

If the outlet temperature fluctuates, rising

above the normal range and then drops

below the normal range.

Follow Section 3.1 & 3.2 to decommission the 

station for repair. Follow Section 4.2 to adjust 

the V1 Mixing Valve outside the unit. If the valve 

cannot be adjusted correctly a replacement WWM 

Diaphragm Actuator is required. (See section 4.3 for 

replacement instructions)

Cold Water Only

Verify that the hot water flow pressure is adjusted 

slightly high than the cold water flow pressure as 

per the factory’s installation instructions. Follow 

Section 3.1 & 3.2 to decommission the station for 

repair. Remove the V4 Control Valve for testing 

(See section 4.4). If the V4 tests correctly Follow 

Section 4.2 to adjust the V1 Mixing Valve outside 

the unit. If the valve cannot be adjusted correctly a 

replacement WWM Diaphragm Actuator is required. 

If the V1 Mixing Valve is properly adjusted verify 

that the hot water supply is not blocked before 

replacing the WWM Diaphragm Actuator by slowing 

opening the hot water supply valve.

Unit Runs Slightly Off Set-Point

Minor adjustments can be made to the V1. (See 

section 4.1)

1. 

Remove the cap nut located on the top of the diaphragm head with a 1” wrench.

2. 

Loosen calibration lock nut with a 7/16” wrench.

3. 

Use a marking pen to make a reference mark so that the calibration screw can be reset to 

the original location if needed.

4. 

Use a 1/8” hex key to adjust the calibration screw while the unit is running. Turning the 

screw counter clock-wise will raise the temperature and turning the screw clock-wise will 

lower the temperature. The calibration screw should only be adjusted a ½ turn at a time. 

Allow the unit to stabilize for at least one minute after adjustment before trying to make 

other adjustments.

5. 

Once the necessary adjustments are made tighten the lock nut onto the calibration screw.

6.  Re-install the cap nut making sure the face seal does not get pinched. Snug the acorn nut 

with a 1” wrench.

Before beginning repairs read and understand Section 3.1. The Station should be tested after all 

adjustments are completed.

Содержание THERM-O-MIX WWM

Страница 1: ...THERM O MIX WWM STATION Troubleshooting Manual www ThermOmegaTech com 1 877 379 8258...

Страница 2: ...rs V1 Mixing Valve Adjustment Instructions with the Unit Running V1 Mixing Valve Adjustment Instructions with the WWM Diaphragm Removed WWM Diaphragm Actuator VI Mixing Valve Replacement Instructions...

Страница 3: ...ode pressure sensitive diaphragm overrides and closes hot port during over temperature or loss of hot water supply at V1 Page 2 Section 1 2 Recommended Tools Section 1 3 Check List The following is a...

Страница 4: ...en the Station outlet exceeds approximately 95 F thus closing the hot inlet port on the mixing valve With the hot port closed no hot water can flow to the mixing valve so the Station outlet is cold wa...

Страница 5: ...iod of time may be needed depending on the size and length of supply piping 3 With the system activated close the cold water supply valve to the station 4 See Section 4 0 for individual valve adjustme...

Страница 6: ...for repair Remove the V4 Control Valve for testing See section 4 4 If the V4 tests correctly Follow Section 4 2 to adjust the V1 Mixing Valve outside the unit If the valve cannot be adjusted correctl...

Страница 7: ...ol and the cap is 160 175 in See Appendix 5 6 6 Place stainless steel sensor into a water bath with a temperature 5 F below the set point for five minutes Verify that the top of the spool is sitting o...

Страница 8: ...y and tighten with 1 1 2 wrench 7 Position the diaphragm housing so that the adaptor fittings are pointing to the side of the body with the braided hoses Note To position the diaphragm housing rotate...

Страница 9: ...tside connections on the V4 Control Valve require orifice plates to be installed Place an orifice plate in the female end of the hose and carefully thread the hose on to the proper male fitting Note t...

Страница 10: ...or referenced part Appendix 4 The Station checklist should be used whenever troubleshooting or repair work is done on a unit The Station Serial Number is located on the V1 Mixing Body The checklist c...

Страница 11: ...AGM HEAD V1 VALVE PORT C COLD WATER INLET 1 NPT FEMALE V4 VALVE COLD WATER TEPID WATER HOT WATER DIAPHRAGM SUPPLY WATER DIAPHRAGM DRAIN WATER THERMAL SENSING LINE DIAPHRAGM SUPPLY HOSE B DIAPHRAGM SUP...

Страница 12: ...OT WATER AVAILIBLE IS MIXING VALVE OUTLET ABOVE 95 F V4 OPEN DIAPHRAGM ACT OVERRIDE MIXING VALVE V1 BLENDS HOT COLD WATER TO SET POINT IS COLD WATER SUPPLY ABOVE 95 F V4 OPEN DIAPHRAGM ACT OVERRIDE DI...

Страница 13: ...5 ORIFICE ORIFICE ORIFICE V4 CONTROL VALVE V1 MIXING VALVE CAP NUT DIAPHRAGM HEAD PORT B HOT WATER INLET 1 NPT FEMALE FEMALE 1 1 4 NPT HOSE ASSEMBLY 7 5 PORT C COLD WATER INLET 1 NPT FEMALE PORT A TEP...

Страница 14: ...tation supplying tempered water to anything other than the Safety Shower Station YES NO If YES explain __________________________________________________________________________ ______________________...

Страница 15: ...ge 14 APPENDIX 5 WWM Diaphragm Actuator V1 Mixing Valve Line Drawing SET POINT 5 F CARTRIDGE CAP O RING SPOOL THERMOSTATIC ACTUATOR CAP NUT FOR ADJUSTMNET SET SCREW 1 HEX 1 1 2 HEX SET POINT 5 F 160 1...

Страница 16: ...Page 15 APPENDIX 6 WWM Diaphragm Actuator V1 Mixing Valve Adjustment Photo Loosen lock nut Adjust calibration screw...

Страница 17: ...ide WWM Diaphragm Actuator WARNING This product can expose you to chemicals for example lead nickel acrylonitrile which are known to the State of CA to cause cancer birth defects or reproductive harm...

Отзывы: