Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 34
o
The toggle between comfort operation to lowering mode is made delayed by
the adjusted time(s), e.g. when using the wireless chair or motion detector.
Control Property
Basic Set Point
o
Basic set point for control
Proportional range Xp
o
adjustable between 0-10 K
Running-after time „Tn“
o
Reset time of integral range, adjustable from 0-255 min
o
If the running-after time „Tn“ is set to 0, the same is deactivated
Lower and upper control variable limit
o
Limit of control output
Output
In the field “Output“ the current status of the output can be displayed by activating
the hook mark.
4.3.8.2 Register Card Sensors
1 temperature sensor can be learned-in
Window contacts are “Or“-operated, i.e. all window contacts must be closed
If the window is opened, the controller switches to 100% if the antifreeze
temperature is fallen below.
Devices for night lowering are “OR“-operated.
4.3.8.3 Changeover-Function
Changeover function is only on SRC-ADO-Type2 available. Changeover function is used
by 2-pipe Systems. Changeover between heating and cooling could be realized by useing
micro switch (SR04/SR07 MS) or an extra digital input module (SR65-DI).