12
40.021.119 - rev. 00 - 2019
IMAC 4000 GAS US
English
Record the maintenance details in table A in the
appendix of this manual.
7
SPARE PARTS
Before use we advise you to have spare parts in
store, see table B in the appendix of this manual.
8
TECHNICAL INFORMATION
See for technical specifications table C in the
appendix of this manual.
9
INSTALLING ACCESSORIES
9.1
Flue (Fig. 3)
The convector heater has a flue connection.
1. Slide a flue (B) over the connection (C).
Caution
The flue must be pointed upwards. Do
not let the flue point sideways. An angle
of 45° is acceptable; the length of the
flue should be at least 1000 mm.
2. Place a rain cover (A) on the end of the flue.
Fault
Nr.
Cause
Solution
Who
The burner will
start, a flame has
been formed but
the burner stops.
29
The ionization probe is
malfunctioning or is defective.
Check the ionization probe.
Clean or replace if necessary
Dealer
30
There are problems with the
polarity or the connection to
earth.
Check the electrical
connections. Correct if
necessary.
User
The convector
heater cannot be
switched off.
31
The magnet valve or valves will
not close.
Close the cock, see fig. 8 (B).
User
Contact your dealer.
Dealer
The convector
heater stops.
32
An overheating problem has
occurred in the convector
heater.
Reduce the resistance at the
outlet.
User
Reset the thermostat.
User
Contact the dealer if the error is
repeated.
Dealer
The convector
heater stops
burning. The reset
button lights up.
33
The fuel-supply line or the fuel
filter is leaking.
Check and replace if necessary. User
34
The protective grill of the air
inlet is dirty or clogged.
Clean the grill.
User
35
The heat exchanger is blocked. Clean the heat exchanger.
Dealer
The convector
heater is producing
white smoke.
36
There is air in the fuel system.
Check the fuel-supply line for
leakage.
User
Burner malfunction:
the indicator light
(red) is on.
37
There is no fuel.
Check whether there is fuel in
the tank.
User
The ioniziation probe is dirty.
Clean the ioniziation probe.
User
The ioniziation probe is
defective.
Replace the ioniziation probe.
Dealer
The frequency
controller has a
fault: the indicator
light (red) is on.
41
The motor of the main fan has a
problem.
Reset the frequency controller:
press the button, see fig. 5 (G).
User
Contact the dealer if the error is
repeated.
Dealer
Содержание IMAC 4000 GAS US
Страница 1: ...IMAC 4000 GAS US USER MANUAL...
Страница 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K L M N O P Q R 1 2 3 4...
Страница 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 5 7...
Страница 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...
Страница 14: ...14 40 021 119 rev 00 2019 IMAC 4000 GAS US English Date Description Maintenance or Failure Action by A...
Страница 15: ...15 40 021 119 rev 00 2019 English IMAC 4000 GAS US Date Description Maintenance or Failure Action by...
Страница 17: ...17 40 021 119 rev 00 2019 English IMAC 4000 GAS US...
Страница 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...