IMAC 4000 GAS US

5  

MAINTENANCE

5.1  

Maintenance table

Use the table in this booklet to record performed

maintenance after each winter season.

5.2  

General

Use the table in this booklet to record performed

maintenance after each winter season.

When the convector heater is to be stored for a

longer period of time:

1.  Switch on the convector heater for three

     minutes. This will protect the fuel pump

     against corrosion.

2.  Make sure the burner head is free from dust

     and deposit.

     A dirty heater head will cause insufficient

     combustion, resulting in the development of

     soot and carbon monoxide and causing

     damage to the burner room.

3.  Close the valve of the fuel supply.

4. Disconnect the power plug.

 

Warning

 

Switch off power during maintenance!

 Hot

 

Do not touch the flue and air outlet!

 

Wait until the flue and the air outlet have

 

cooled down sufficiently before carrying

 

out any maintenance.

5.3  

V-belts (Fig. 7 )

Impression

V-belt tension

13 mm

32,2 N

1. Remove the upper and lower side panels (A).

2. Lower the motor (B) by turning the adjusting

nuts (C).

3. Remove the old V-belts (D).

Install new V-belts in reverse order.

 

Caution

 

Tension the V-belts according to the

 table.

Description yearly check.

Who

Check the general condition of the fans, ignition electrode, ionization probe, burner,

electrical installation, combustion room, and heat exchanger.

Dealer

Check the fuel lines for dirt and leakage.

User

Check the air inlet for dirt

User

Check the fan of the burner for corrosion and dirt.

User

Check the fan for corrosion and dirt.

User

Check the fan motor for proper operation

User

Check the ionization probe for signs of damage. Make sure the ionization probe is free

from dust and deposit.

User

Check the settings of the ignition electrode.

Dealer

Check the distributor head for dust, etc.

Dealer

Clean the heat exchanger.

Dealer

Clean the inlet/outlet.

User

Check the V-belts.

User

Check the torque of the armatures. The torque value should be 60 Nm.

User

Содержание IMAC 4000 GAS US

Страница 1: ...IMAC 4000 GAS US USER MANUAL...

Страница 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K L M N O P Q R 1 2 3 4...

Страница 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 5 7...

Страница 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...

Страница 5: ...bility For warranty and liability see general warranty regulations Environment Note The convector heater is made of various metals and synthetic materials The heater also contains electronic parts whi...

Страница 6: ...ible mixture that is ignited by the spark between the electrodes The light of the flame that is created will activate the photocell This photocell checks whether a good combustion is brought about In...

Страница 7: ...s Dizziness disorientation Difficulty breathing feels of being suffocated Proper ventilation air exchange OSHA 29 CFR 1926 57 to support combustion and maintain acceptable air quality shall be provide...

Страница 8: ...Caution Only use natural gas of the family I2H and propane of the family 13P 4 Make sure there is sufficient distance between the wall and the air inlet Minimum distance is 1 m 5 Ensure that the heate...

Страница 9: ...efore carrying out any maintenance 5 3 V belts Fig 7 Impression V belt tension 13 mm 32 2 N 1 Remove the upper and lower side panels A 2 Lower the motor B by turning the adjusting nuts C 3 Remove the...

Страница 10: ...7 The air pressure switch has not closed Check the air hoses for dirt Replace if necessary Dealer 8 The maximum thermostat is stopping the convector heater Check and correct the air flow Reset the con...

Страница 11: ...orcer plate are incorrect or dirty Correct the settings of the distributor holder and the forcer plate Clean the nozzle and the forcer plate Dealer 23 Exhaust opening or flue connection is in poor con...

Страница 12: ...e switched off 31 The magnet valve or valves will not close Close the cock see fig 8 B User Contact your dealer Dealer The convector heater stops 32 An overheating problem has occurred in the convecto...

Страница 13: ...ion Check the temperature resistance of the hose used Contact your dealer for information about the maximum length of the exhaust hoses bends manifolds and hose clamps The maximum static pressure in t...

Страница 14: ...14 40 021 119 rev 00 2019 IMAC 4000 GAS US English Date Description Maintenance or Failure Action by A...

Страница 15: ...15 40 021 119 rev 00 2019 English IMAC 4000 GAS US Date Description Maintenance or Failure Action by...

Страница 16: ...pressure propane PSI iwc 0 27 5 8 0 27 5 8 0 32 8 8 Inlet Burner pressure natural gas PSI iwc 0 04 1 2 0 04 1 2 0 08 2 1 Air capacity m hr 18 000 24 000 24 000 CFM 10 595 14 715 14 715 Max pressure P...

Страница 17: ...17 40 021 119 rev 00 2019 English IMAC 4000 GAS US...

Страница 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...

Страница 19: ...care but Thermobile Industries B V cannot be held liable for possible errors in the information or the consequences thereof The information provided herein may not be reproduced and or published in an...

Страница 20: ...NDUSTRIES BV Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com 40 021 119...

Отзывы: