HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the
Controller ON.
3.
Automatically the parameter list of the “Hot Key” is downloaded into the
Controller memory, the “doL” message is blinking followed a by flashing “End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit
off and then on if you want to restart the download again or remove the “Hot key” to
abort the operation.
12.
ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output according to par.
“Con” and “COF”
“P2”
Evaporator probe failure
Defrost end is timed
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
“dA”
Door open
Compressor and fans restarts
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm (i1F=bAL)
All outputs OFF.
“CA”
Pressure switch alarm (i1F=PAL)
All outputs OFF
12.1
ALARM RECOVERY
Probe alarms “P1” and “P2” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check
connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat
temperature returns to normal values and when defrost starts.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
13.
TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR60C frontal 32x74 mm; depth 60mm;
Mounting: XR60C panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block
≤
2,5 mm
2
wiring.
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
±
10%, 50/60Hz, 110Vac
±
10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 2 NTC or PTC probes.
Digital input: free contact
Relay outputs
compressor: SPST relay 8(3) A, 250Vac or SPST relay 16(6)A; 250Vac
defrost: SPDT relay 8(3) A, 250Vac
fan: SPST relay 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: normal;Software class: A.
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 20
÷
85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
14.
CONNECTIONS
14.1
XR60C – 12VAC/DV OR 24 VAC/DV
N.C.
Line
8(3)A250V
a
8(3)A
Max
16A
Comp
Def
Fan
Ev
ap
.
Ro
om
Hot Key
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.
24Vac/dc supply: connect to the terminals 7 and 8.
14.2
XR60C – 120VAC OR 230 VAC
N.C.
Line
8(3)A250V
a
8(3)A
Max
16A
Comp
Def
Fan
Ev
ap
.
Ro
om
Hot Key
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.
120Vac supply: connect to the terminals 6 and 7.
15.
DEFAULT SETTING VALUES
Label
Name
Range
°C/°F
Set
Set point
LS÷US
-5/0
Hy
Differential
0,1
÷
25.5°C/ 1
÷
255°F
2/4
LS
Minimum set point
-50°C
÷
SET/-58°F
÷
SET
-50/-58
US
Maximum set point
SET
÷
110°C/ SET
÷
230°F
110/230
Ot
Thermostat probe calibration
-12
÷
12°C /-120
÷
120°F
0
P2P Evaporator probe presence
n=not present; Y=pres.
y
OE
Evaporator probe calibration
-12
÷
12°C /-120
÷
120°F
0
OdS Outputs delay at start up
0÷255 min
0
AC
Anti-short cycle delay
0
÷
50 min
1
CCt Continuos cycle duration
0.0÷24.0h
0.0
COn Compressor ON time with faulty probe
0
÷
255 min
15
COF Compressor OFF time with faulty probe
0
÷
255 min
30
CF
Temperature measurement unit
°C
÷
°F
°C/°F
rES Resolution
in=integer; dE= dec.point
dE/-
Lod Probe displayed
P1;P2
P1
tdF
Defrost type
EL=el. heater; in= hot gas
EL
dtE
Defrost termination temperature
-50
÷
50 °C
8/46
IdF
Interval between defrost cycles
1
÷
120 ore
6
MdF (Maximum) length for defrost
0
÷
255 min
30
dSd Start defrost delay
0÷99min
0
dFd Displaying during defrost
rt, it, SEt, DEF
it
dAd MAX display delay after defrost
0 ÷ 255 min
30
Fdt
Draining time
0÷120 min
0
dPo
First defrost after startup
n=after IdF; y=immed.
n
dAF Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
Fnc Fan operating mode
C-n, o-n, C-y, o-Y
o-n
Fnd Fan delay after defrost
0÷255min
10
Fct
Differential of temperature for forced
activation of fans
0÷50°C
10
FSt
Fan stop temperature
-50÷50°C/-58÷122°F
2/35
ALc Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab
ALU MAXIMUM temperature alarm
Set
÷
110.0°C; Set÷230°F
110/230
ALL Minimum temperature alarm
-50.0°C
÷
Set/ -58°F
÷
Set
-50/-58
ALd Temperature alarm delay
0
÷
255 min
15
dAO Delay of temperature alarm at start up
0
÷
23h e 50’
1.30
i1P
Digital input polarity
oP=opening;CL=closing
CL
i1F
Digital input configuration
EAL=extern. alarm; bAL=lock regulation;
PAL=press. switch; dor=door switch;
dEF=defrost; LHt=disabled; Htr = heating
- cooling
dor
did
Digital input alarm delay
0÷255min
15
Nps Number of activation of pressure switch
0 ÷15
15
odc Compressor and fan status when open
door:
no = normal; Fan = Fan OFF; CPr =
Compr. OFF; F_C = Compr & fan OFF
F-C
PbC Kind of probe
Ptc; ntc
ntc/Ptc
dP1 Room probe display
--
--
dP2 Evaporator probe display
--
--
rEL
Software release
--
2.7
Ptb
Map code
--
-
Hidden parameters