All installations and services must be performed by qualified service personnel.
34
NOTICE: A U-tube manometer
, measuring pressure in inches of water column,
is recommended
for
all gas pressure measurements. However,
an aneroid pressure gauge
, in good working condition,
capable of reading pressure changes of 0.05 in. W.G., or less, that was
recently calibrated
(within
the last year),
is a satisfactory alternate
.
These two (2) devices will be considered as equivalent and
interchangeable. Either device is referred to below as a “pressure gauge”
NOTICE:
This 2-stage gas valve has two separate gas pressure regulators.
Checks and
adjustments must be made at both high fire (high adjustment) and low fire (low adjustment).
1.
Shut off the gas
at the automatic gas control valve (turn gas control knob to the OFF position).
2. Remove the outlet pressure tap plug from gas burner manifold and connect a pressure gauge.
Refer to Figure 22, below.
Figure 22: Exploded View of CDX/CHX Gas Control System
3. Turn on the gas at the automatic gas control valve (turn gas control knob to the ON position).
4. Adjust the room thermostat so the furnace will
operate on low fire
only
.
Содержание CDX1-100N
Страница 21: ...All installations and services must be performed by qualified service personnel 15 Figure 7...
Страница 55: ...All installations and services must be performed by qualified service personnel 49...
Страница 57: ...All installations and services must be performed by qualified service personnel 51...
Страница 58: ...All installations and services must be performed by qualified service personnel 52 Appendix B Wiring Diagrams...
Страница 59: ...All installations and services must be performed by qualified service personnel 53...