111
Fault Indication Diagnosis
The following fault indicator functions will be held in mem-
ory and displayed on the temperature readout display when
the Alarm [CODE] key is pressed. There are several alarm
types that can be indicated by the controller.
SHUTDOWN ALARMS
Shut down alarms will turn the unit off immediately upon
detection. They are indicated by a flashing alarm symbol.
Shutdown alarms must be corrected and cleared before the
unit can be restarted.
NOTE: It is possible to clear a shutdown alarm with the
unit switched of]; however the unit will shut down again
when the alarm reoccurs.
CHECK ALARMS
Check alarms act as prompts to take corrective action before
a problem becomes severe. They are indicated by steady
alarm symbol. They may be cleared, but will reoccur until
corrected.
STORED ALARMS
Stored alarms are indicated by a steady alarm symbol that is
displayed for 30 seconds after the On-Off switch is turned
ON.
After 30 seconds, the Stored Alarm will disappear from the
display.
View and write down each fault code as it is displayed.
When all codes have been viewed and correct (serviced or
repaired), press the CLEAR key to clear each alarm from
the display.
Alarm Code Legend
(ST) = Stored Alarm
(CH) = Check Alarm
(SH) = Shutdown Alarm
(*) = Must be repaired by dealer
(**) = Possibly may be repaired by operator
(***)Should be cleared by service personnel only
Alarm Code Diagnosis
00 No Fault
01 (SH) (*) (**) Microprocessor Power Up Reset
Possible cause: defective microprocessor.
Test procedure: replace microprocessor.
02 (CH) (*) Evaporator Coil Sensor
Possible cause: open sensor lead.
Test procedure: test for continuity.
Possible Cause: Shorted sensor lead.
Test Procedure: Test for ground.
Possible cause: defective sensor.
Test procedure: test sensor voltage.
Possible cause: defective microprocessor.
Test procedure: replace microprocessor.
NOTE: Control changes to discharge air sensor.
Содержание Super II SR+
Страница 4: ......
Страница 10: ...ii ...
Страница 14: ...4 ...
Страница 22: ...Unit Description Rev 6 98 12 Front View AEA1350 ...
Страница 23: ...Unit Description Rev 6 98 13 Right Side Door Open AEA1351 ...
Страница 24: ...Unit Description Rev 6 98 14 Left Side Doors Open AEA1352 ...
Страница 26: ...Operating Instructions Rev 6 98 16 Control Box Cover AEA1354 ...
Страница 34: ...24 ...
Страница 42: ...Electronic Controls Rev 6 98 32 SOFTWARE REVISION 04XX ALARMS AEA1358 ...
Страница 82: ...72 ...
Страница 90: ...80 ...
Страница 116: ...106 ...
Страница 120: ...110 ...
Страница 130: ...120 ...
Страница 141: ...131 Schematic Diagram SBIII SII RMNII 30 SR MPIV ...
Страница 142: ...132 Wiring Diagram SII SBIII RMN30 SR MPIV Page 1 of 4 ...
Страница 143: ...133 Wiring Diagram SII SBIII RMN30 SR MPIV Page 2 of 4 ...
Страница 144: ...134 Wiring Diagram SII SBIII RMN30 SR MPIV Page 3 of 4 ...
Страница 145: ...135 Wiring Diagram SII SBIII RMN30 SR MPIV page 4 of 4 ...