Loading and Enroute Inspections
168
Enroute Inspections
Complete the following enroute inspection every four hours.
This will help minimize temperature related problems.
Inspection Procedure
1.
Verify setpoint is correct.
2.
Check the return air temperature reading. It should be
within the desired temperature range.
3.
Initiate a manual defrost cycle after each enroute
inspection.
Inspection Troubleshooting
1.
If a temperature reading is not within the desired
temperature range, refer to the troubleshooting table on the
following pages. Correct problem as required.
2.
Repeat the Enroute Inspection every 30 minutes until the
compartment temperature is within the desired
temperature range. Stop the unit if the compartment
temperature is not within the desired temperature range on
two consecutive 30 minute inspections, especially if the
compartment temperature appears to be moving away
from the setpoint.
3.
Immediately contact the nearest Thermo King Service
Center or your company office.
4.
Take all necessary steps to protect and maintain proper
load temperature.
CAUTION: Stop the unit if the compartment
temperature remains higher than the desired
temperature range from the setpoint on two
consecutive 30 minute inspections. Contact the
nearest Thermo King Service Center or your
company office immediately. Take all necessary steps
to protect and maintain proper load temperature.
Loading and Enroute Inspections
168
Enroute Inspections
Complete the following enroute inspection every four hours.
This will help minimize temperature related problems.
Inspection Procedure
1.
Verify setpoint is correct.
2.
Check the return air temperature reading. It should be
within the desired temperature range.
3.
Initiate a manual defrost cycle after each enroute
inspection.
Inspection Troubleshooting
1.
If a temperature reading is not within the desired
temperature range, refer to the troubleshooting table on the
following pages. Correct problem as required.
2.
Repeat the Enroute Inspection every 30 minutes until the
compartment temperature is within the desired
temperature range. Stop the unit if the compartment
temperature is not within the desired temperature range on
two consecutive 30 minute inspections, especially if the
compartment temperature appears to be moving away
from the setpoint.
3.
Immediately contact the nearest Thermo King Service
Center or your company office.
4.
Take all necessary steps to protect and maintain proper
load temperature.
CAUTION: Stop the unit if the compartment
temperature remains higher than the desired
temperature range from the setpoint on two
consecutive 30 minute inspections. Contact the
nearest Thermo King Service Center or your
company office immediately. Take all necessary steps
to protect and maintain proper load temperature.
Содержание SB-210+
Страница 1: ...Operator s Manual SB 210 SB 310 Operator s Manual SB 210 SB 310 TK 53942 2 OP Rev 1 11 09 ...
Страница 13: ...12 Introduction 12 ...
Страница 23: ...22 EPA Emission Control System Warranty Statement 22 ...
Страница 45: ...44 Remote Status Display Optional 44 ...
Страница 109: ...108 Figure 77 Pretrip Test Screen Sequence Operating Instructions 108 Figure 77 Pretrip Test Screen Sequence SELECT Key ...
Страница 117: ...116 Operating Instructions 116 1 Product Setpoint Soft Key Figure 85 Standard Display with Product Setpoint Soft Key 1 ...
Страница 129: ...128 Operating Instructions 128 ...
Страница 189: ...188 Maintenance Inspection Schedule 188 ...
Страница 191: ...190 Warranty 190 ...
Страница 205: ...204 Serial Number Locations 204 ...