Operating Instructions
106
Initiating a Pretrip Test
Before initiating a Pretrip Test, clear all alarm codes.
To stop a Pretrip Test at any time, turn the unit off.
Use the following procedure to initiate a Full Pretrip or a
Running Pretrip. A Running Pretrip can also be initiated by
starting at step 3 with the unit running.
1.
If the unit is running, press the
O
FF
key to stop the unit.
2.
Press the
O
N
key to turn the unit on.
3.
To initiate a Full Pretrip press the
M
ENU
soft key as soon
as the Standard Display appears and before the unit starts.
To initiate a Running Pretrip let the unit start before
pressing the
M
ENU
soft key on the Standard Display.
4.
Press the
N
EXT
soft key until the Pretrip Screen appears.
See Figure 77.
5.
Press the
S
ELECT
soft key to start a Pretrip.
NOTE: If all alarms were not cleared, a prompt appears
as shown below. Press the
E
XIT
key to exit the Pretrip
Test, clear all alarms and repeat the Pretrip Test.
1.
Menu Soft Key
Figure 75: Standard Display
1
1.
Press Exit Soft Key
Figure 76: No Pretrip Alarm Active Display
OFF
ON
NO PRETRIP -- ALARM ACTIVE
EXIT
ARA835
1
Operating Instructions
106
Initiating a Pretrip Test
Before initiating a Pretrip Test, clear all alarm codes.
To stop a Pretrip Test at any time, turn the unit off.
Use the following procedure to initiate a Full Pretrip or a
Running Pretrip. A Running Pretrip can also be initiated by
starting at step 3 with the unit running.
1.
If the unit is running, press the
O
FF
key to stop the unit.
2.
Press the
O
N
key to turn the unit on.
3.
To initiate a Full Pretrip press the
M
ENU
soft key as soon
as the Standard Display appears and before the unit starts.
To initiate a Running Pretrip let the unit start before
pressing the
M
ENU
soft key on the Standard Display.
4.
Press the
N
EXT
soft key until the Pretrip Screen appears.
See Figure 77.
5.
Press the
S
ELECT
soft key to start a Pretrip.
NOTE: If all alarms were not cleared, a prompt appears
as shown below. Press the
E
XIT
key to exit the Pretrip
Test, clear all alarms and repeat the Pretrip Test.
1.
Menu Soft Key
Figure 75: Standard Display
1
1.
Press Exit Soft Key
Figure 76: No Pretrip Alarm Active Display
OFF
ON
NO PRETRIP -- ALARM ACTIVE
EXIT
ARA835
1
Содержание SB-210+
Страница 1: ...Operator s Manual SB 210 SB 310 Operator s Manual SB 210 SB 310 TK 53942 2 OP Rev 1 11 09 ...
Страница 13: ...12 Introduction 12 ...
Страница 23: ...22 EPA Emission Control System Warranty Statement 22 ...
Страница 45: ...44 Remote Status Display Optional 44 ...
Страница 109: ...108 Figure 77 Pretrip Test Screen Sequence Operating Instructions 108 Figure 77 Pretrip Test Screen Sequence SELECT Key ...
Страница 117: ...116 Operating Instructions 116 1 Product Setpoint Soft Key Figure 85 Standard Display with Product Setpoint Soft Key 1 ...
Страница 129: ...128 Operating Instructions 128 ...
Страница 189: ...188 Maintenance Inspection Schedule 188 ...
Страница 191: ...190 Warranty 190 ...
Страница 205: ...204 Serial Number Locations 204 ...