Unit Operation with TG-VI Controller
51
8.
If any alarms were not cleared before starting the Unit Self
Check, they will be displayed at this time. They can be
cleared by pressing the
E
NTER
key.
9.
The controller will now automatically preheat and start the
diesel engine.
10. All segments of the display will be lighted at the same
time.
11. All programmable settings will be sequentially displayed.
These settings may be verified by the operator if
necessary.
12. The diesel engine RPM is checked in both high and low
speed.
13. The operation of the defrost damper is checked.
14. The ability of the unit to cool in low speed is checked.
15. The ability of the unit to heat is checked.
16. A second low speed cooling capacity check is performed
to insure that the unit can switch from cool to heat and
back to cool.
17. At the completion of the Unit Self Check, the check results
will appear on the display. They will remain until any key
on the controller is pressed. Check results are shown as
either PASS, CHEC or FAIL:
[PASS]—The unit is running and no alarms have been
recorded. The unit has passed the USC.
[CHEC]—The unit is running but Check Alarms have
been recorded.
[FAIL]—The unit has shut down. View and correct any
alarms. See “Figure 29: Alarm Symbol Location,” on
page 61.
Unit Operation with TG-VI Controller
51
8.
If any alarms were not cleared before starting the Unit Self
Check, they will be displayed at this time. They can be
cleared by pressing the
E
NTER
key.
9.
The controller will now automatically preheat and start the
diesel engine.
10. All segments of the display will be lighted at the same
time.
11. All programmable settings will be sequentially displayed.
These settings may be verified by the operator if
necessary.
12. The diesel engine RPM is checked in both high and low
speed.
13. The operation of the defrost damper is checked.
14. The ability of the unit to cool in low speed is checked.
15. The ability of the unit to heat is checked.
16. A second low speed cooling capacity check is performed
to insure that the unit can switch from cool to heat and
back to cool.
17. At the completion of the Unit Self Check, the check results
will appear on the display. They will remain until any key
on the controller is pressed. Check results are shown as
either PASS, CHEC or FAIL:
[PASS]—The unit is running and no alarms have been
recorded. The unit has passed the USC.
[CHEC]—The unit is running but Check Alarms have
been recorded.
[FAIL]—The unit has shut down. View and correct any
alarms. See “Figure 29: Alarm Symbol Location,” on
page 61.
Содержание SB-200TG
Страница 1: ...Operator s Manual SB 200TG Operator s Manual SB 200TG TK 53598 2 OP Rev 0 02 07...
Страница 7: ...6 Table of Contents 6...
Страница 11: ...10 Introduction 10...
Страница 21: ...20 EPA Emission Control System Warranty Statement 20...
Страница 43: ...42 TG VI Controller Description 42...
Страница 45: ...44 Remote Status Light Optional 44...
Страница 83: ...82 Alarm Codes 82...
Страница 103: ...102 Warranty 102...
Страница 116: ...115 Figure 38 Unit Serial Number Plate Serial Number Locations 115 Figure 38 Unit Serial Number Plate...
Страница 117: ...116 Serial Number Locations 116...