ENGLISH

IMPORTANT!

Please read before installation

This heat pump system meets strict safety and operating 
standards.
For the installer or service person, it is important  to install or 
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

•  Carefully read this instruction booklet before beginning.
•  Follow each installation or repair step exactly as shown.
•  Observe all local, state and national electrical  codes.
•  Pay close attention to all warning and caution notices given in 

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result 
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result 
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and 
maintenance conditions.
If you require help for a special problem, contact our sale/service 
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper 
installation or maintenance service, including failure to follow the 
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system 

and then the wiring one; proceed in the reverse orden when 
removing the units.

    

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE 
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, 
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT 
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing 

are completed or reconnected and checked, to ensure the 
grounding.

•  Highly dangerous electrical voltages are used in this system. 

Carefully refer to the wiring diagram and these instructions 
when wiring.

  Improper connections and inadequate grounding can cause 

accidental injury and death

.

• 

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection 

different from the ground connection.

•  Connect all wiring tightly. Loose wiring may cause overheating 

at connection points and a possible fire hazard.

•  Do not allow wiring to touch the refrigerant tubing, compressor, 

or any moving parts of the fan.

•  Do not use multi-core cable when wiring the power supply and 

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor 
units. Get a partner to help, and bend your knees when lifting to 
reduce strain on your back. Sharp edges or thin aluminium fins 
on the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-
weight. It may be necessary to build a strong wooden or metal 
frame to provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent 
“sweating”, which can cause dripping and water damage to 
walls and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation 
for the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal 
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than 
drifting snow. Provide snow vents.

When connecting refrigerant tubing

•  Keep all tubing runs as short as possible.
•  Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the 

flare and union tubes before connecting them;  screw by hand 
and  then tighten the nut with a torque wrench for a leak-free 
connection.

•  Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either 
narrow or wide. Therefore, to avoid confusion, the refrigerant 
tubing for your particular model is specified as narrow tube for 
liquid, wide tube for gas.

When servicing

•  Turn the power OFF at the main power board  before opening 

the unit to check or repair electrical parts and wiring.

•  Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that 

no metal scraps or bits of wiring have been left inside the unit 
being serviced.

• Ventilate the room during the installation or testing the 

refrigeration system; make sure that, after the installation, no 
gas leaks are present, because this could produce toxic gas 
and dangerous if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

7

 

Содержание AFEX 065 MONO

Страница 1: ...ENGLISH ITALIANO AFEX 065 MONO ISTRUZIONI D INSTALLAZIONE INSTALLATION INSTRUCTIONS Unit esterna Outdoor unit...

Страница 2: ...o con i tubi refrigeranti il compressore o le parti mobili del ventilatore Nel collegare l alimentazione e le linee di controllo non usare cavi a pi conduttori Usare cavi separati per ciascun tipo di...

Страница 3: ...poggio non livellato Di eseguire fori nelle zone dove si trovano parti elettriche o impianti PREFERIBILE Scegliere aree possibilmente in ombra e leggermente ventilate Fissare l unit alla base di appog...

Страница 4: ...o in rame ricotto e disossidato per refrigerazione per il collegamento tra le unit ed isolato con polietilene espanso di spessore min 8 mm l Tubo in PVC per scarico condensa int 18 mm di lunghezza suf...

Страница 5: ...erna 27 C B S Condizioni Minime in Riscaldamento Temperatura esterna 15 C B S Temperatura interna 5 C B S LIMITI DI FUNZIONAMENTO I UNIT INTERNA UNIT ESTERNA UNIT INTERNA UNIT INTERNA UNIT INTERNA L T...

Страница 6: ...CONFORMIT Questo prodotto marcato in quanto conforme alle Direttive Bassa Tensione n 2014 35 UE Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 with EN 60335 1 20...

Страница 7: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Страница 8: ...ectrical wiring or conduits are located DO Choose places as cool as possible and well ventilated use lug bolts or equal to bolt down the unit reducing vibration and noise Provide a solid base for outd...

Страница 9: ...AL MATERIAL REQUIRED FOR INSTALLATION NOT SUPPLIED 4 ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION NOT SUPPLIED NARROW TUBE LARGE TUBE MODEL INDOOR UNIT OUTER DIAMETER MIN THICKNESS OUTER DIAMETER MIN...

Страница 10: ...C D B 18 C W B Room temperature 27 C D B Heating Minimum conditions Outdoor temperature 15 C D B Room temperature 5 C D B OPERATING LIMITS EG L Tot Total tubing length L1 L2 L3 Ln Maximum tubing lengt...

Страница 11: ...06 A1 2009 A2 2011 EN 55014 2 1997 A1 2001 A2 2008 EN 61000 3 2 2006 A1 2009 A2 2009 EN 61000 3 3 2008 RoHS2 no 2011 65 EU Regulation EU no 206 2012 of 6 march 2012 concerning the specifications for e...

Страница 12: ...MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B INSTALLATION MANUAL EMIX PORT VEDI IL MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B INST...

Страница 13: ...O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B INSTALLATION MANUAL EMIX PORT VEDI IL MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B INSTALLATION MANUAL EMIX PORT VEDI IL...

Страница 14: ...R UNIT EMIX PORT VEDI IL MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B INSTALLATION MANUAL EMIX PORT VEDI IL MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SE...

Страница 15: ...8 mm Insulation Utilizzare del tubo in rame isolato Tagliare con lunghezza maggiorata di 30 50 cm oltre la distanza tra le unit Use insulated copper tube Cut approximate 30 50 cm longer than actual d...

Страница 16: ...ubes Hold the tube end downward and be sure that no dirt falls into the tube EN I F Cartellare le estremit dei tubi ricordandosi di infilare i bocchettoni rimossi dalle unit Insert flare nuts removed...

Страница 17: ...spetto aria ed umidit nel circuito frigorifero provocano effetti dannosi al sistema Air purging of internal unit and refrigerant tubes Connect the vacuum pump to the outside unit as shown in the figur...

Страница 18: ...re i cappucci ed il bocchettone stringere con momento torcente di 200 kg cm Le operazioni descritte dalla lettera N alla lettera O vanno ripetute per il secondo e il terzo circuito Le unit interne van...

Страница 19: ...ICE VALVES La valvola di servizio del rubinetto dell unit esterna da utilizzare per il vuoto del sistema ripristino carica refrigerante e misurazione della pressione di esercizio del tipo Schrader Uti...

Страница 20: ...NUALE INSTALLAZIONE DELL UNITA INTERNA SPECIFICA BEFORE STARTING THE SYSTEM IT IS NECESSARY TO SET THE REFRIGERANT CIRCUIT ADDRESSES THE SETTING HAS TO BE MADE ON THE INDOOR UNITS AND FOR EACH INDOOR...

Страница 21: ...unit without losing gas Pump down is used when the unit is to be moved of before servicing the refrigerant circuit PUMP DOWN I EN PROCEDIMENTO PUMP DOWN PUMP DOWN PROCEDURE B Avviare il condizionator...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...to di tutta la sua produzione le caratteristiche estetiche e dimensionali i dati tecnici gli equipaggiamenti e gli accessori possono essere soggetti a variazione The manufacturer strives to continuous...

Отзывы: