Special functions

When a special function is active, a specific message is shown 

on the display of the device control interface.

Pump activation protection during a Domestic Water re-

quest

If during a domestic water request the delivery temperature of 

the burner is lower than that of the heater the pump will not be 

activated.

Frost protection

The anti-freeze protection function protects the system against 

freezing.

When the anti-freeze function is active, the message “AFro” is 

displayed.

 

The intervention modes are the following:

Burner anti-freeze protection:

 If the temperature of the 

delivery probe of the device drops below 5°C the burn-

er turns on and stays on until the delivery temperature 

exceeds 10°C (with the external probe connected the 

protection activates only with external temperature val-

ues < 10°C).

 

Heating circuit anti-freeze protection:

 If the burner stays 

off for 6 consecutive hours the circulator of the device 

will activate for 5 minutes. If the temperature of the de-

livery probe of the device drops below 5°C the burn-

er turns on and stays on until the delivery temperature 

exceeds 10°C (with the external probe connected the 

protection activates only with external temperature val-

ues < 10°C).

Domestic circuit heater anti-freeze protection

: If the tem-

perature of the heater probe drops below 5°C the burn-

er turns on and the circulator and 3-way diverting valve 

will activate. The burner stays on until the temperature 

of the storage tank sensor exceeds 10°C and the pump 

continues to operate for the post-circulation time. With 

the external sensor connected, protection is activated 

only when the external temperature is < 10°C.

Venting

The function is automatically enabled at the first start-up and at 

each reset of the power supply.

When the function is active, the message “Air” is displayed.

During the venting, the circulator is enabled, so that the air 

which may be present inside the system circuit can exit through 

the automatic drain valve of the device.

The status of the light guide changes to flashing green.

Circulator and 3-way valve activation every 24 hours

Every 24 hours the circulator and 3-way diverting valve are 

activated for 30 seconds (only in heating mode 0,1,4).

This function prevents the circulator and valve from getting 

stuck in a determined position.

Anti-legionella function - With Heater Probe only

The function is automatically enabled when the heater sensor 

is connected, at each reset of the power supply or daily, if nec-

essary.

When the function is on, the message “ALE9” is shown next to 

the storage tank temperature.

The function increases the water temperature inside the heater 

up to 60°C and keeps it for 30 minutes.

Once this time has elapsed, the control box normal operation 

is restored.

Ignition failure

If an ignition or operating anomaly occurs, the thermal unit dis-

play will show a text message (small digit) and a number (large 

digit), which vary according to the anomaly detected.

There are 3 error levels:

- Permanent (Loc)

- Temporary (Err)

- Alerts (AttE)

Permanent Error

The text “Loc” is displayed together with the permanent er-
ror number. The icon 

 indicates that the burner is disabled. 

The equipment must be manually reset by keeping the key 

“ENETER/RESET” pressed.

Temporary Error

The text “Err” is displayed together with the temporary error 

number.
The icon 

 indicates that the burner is disabled.

The lock-out error must be solved.

Contact your local Technical Assistance Centre

Содержание ACQUAHOME R BLU

Страница 1: ...ACQUAHOME R BLU USER MANUAL...

Страница 2: ...recautions that must be observed to ensure the trouble free installation and efficient functioning of your ACQUAHOME R BLU boiler Please accept our renewed thanks for your purchase Thermital CONFORMIT...

Страница 3: ...ety and control devices 5 System layout 6 Control panel 7 Menu navigation 9 Navigation scheme 11 List of user parameters 12 USE 14 Putting into service 14 Preliminary operations 14 Start up 14 Adjustm...

Страница 4: ...for an extended peri od of time perform the operations described later in this manual b This manual is an integral part of the equipment and therefore must be stored carefully and must ALWAYS ac compa...

Страница 5: ...old of 110 C Safety valve intervenes if the boiler pressure exceeds the limit threshold of 3 bar Pressure transducer sends a signal to the electron ic regulator which views and continually checks the...

Страница 6: ...valve 2 Main switch 3 Central heating flow 4 Central heating return 5 Control panel 6 Heating expansion reservoir 7 Burner 8 Drain cock 9 Pump 10 Flame inspection window 11 Boiler body 12 Serial numbe...

Страница 7: ...g the operation after a stop due to an anomaly 5 Navigation keys 6 Main switch located on the equipment rear wall Light Guide displaying STATUS DESCRIPTION Green blinking Thermal unit drain cycle and...

Страница 8: ...e Installer menu 4 Icon displayed when the burner of the equipment is on The icon will be marked with a cross in case of Permanent or Temporary error 5 Icon displayed when the climatic mode operation...

Страница 9: ...setpoint when active available 3 Raise the DHW set point when available 4 Decrease the DHW set point when available 5 ENTER RESET Enters into MENU mode If pressed for more than 5 seconds it resets a p...

Страница 10: ...de keys have the following functions Nr Button Function 1 Exits from the menu and cancels a parameter change 2 Exits from the menu and cancels a parameter change 3 Selects the following menu or increa...

Страница 11: ...11 11 ENGLISH Navigation scheme Modalit visualizzazione base Modalit utente Bar C oppure Example of parameter setting change confirmed change canceled or or or...

Страница 12: ...operation 0 1 0 Info menu 1000 1001 CH flow temperature C 1000 1002 Domestic hot water temperature C 1000 1003 Domestic cold water temperature This parameter is only visible with Par 2035 10 C 1000 10...

Страница 13: ...the setpoint BT Par 2221 45 AT Par 2221 Par 2024 70 AT 45 BT C 2000 2230 Parallel shift of direct Zone Zone 1 climatic curve 10 10 0 C Zone 3 Heating Settings 2000 2303 Zone 3 heating setpoint in 0 an...

Страница 14: ...the thermal unit Bar C close the system load valve Start up Once you have completed all the checks listed above pro ceed as follows to start up the boiler for the first time set the main switch of th...

Страница 15: ...e of the heating temperature setpoint C Increase or decrease the setpoint according to the type of system by using the key of To save the modification made and go back to the initial screen wait for 3...

Страница 16: ...ed only when the external temperature is 10 C Venting The function is automatically enabled at the first start up and at each reset of the power supply When the function is active the message Air is d...

Страница 17: ...Please remember that THE PERSON RESPONSIBLE FOR SYSTEM MANAGEMENT MUST ENSURE THAT PROFES SIONALLY QUALIFIED HEATING ENGINEERS UNDERTAKE PERIODIC MAINTENANCE AND COMBUSTION EFFICIENCY MEASUREMENTS T...

Страница 18: ...Technical Assistan ce Centre The generator triggers a thermal safe ty block Safety thermostat delivery overtemper ature Contact your local Technical Assistan ce Centre No water Contact your local Tec...

Страница 19: ...cycle safely remove the components and dispose of them in a responsible manner in compliance with the installation country s applicable environmental legislation b Adequate sorted waste collection pr...

Страница 20: ...lade Riello 7 37045 Legnago VR www thermital it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are ther...

Отзывы: