9
INSTALLATION INSTRUCTIONS
COLD WATER CONNECTION
HOT WATER CONNECTION
COLD WATER SUPPLY TO WATER HEATER
Refer to the Technical Sheet for the position of connections.
Copper tube of a minimum size of R3/4" (20mm) should be connected to the appliance.
The water inlet connections are R3/4" (20mm) male BSP and requires a union to allow for removal of the
water heater.
Pipe sizing from the cold water supply should be sized according to local BY LAWS for water supply.
ISOLATING VALVE
A gate valve or ball valve must be used on the cold water inlet to the water heater.
THIS REQUIREMENT IS AN AUSTRALIA WIDE REQUIREMENT UNDER
THE NATIONAL PLUMBING CODE.
If the above instruction is not carried out, all warranties on the unit will be voided.
Stop taps or combination stop taps and non-return valves are not to be used.
127(1RSUHVVXUHUHGXFWLRQYDOYHLVUHTXLUHGXQOHVVWKHLQOHWZDWHUSUHVVXUHH[FHHGVN3DDW
any time.
For an appliance intended to be permanently connected to the water mains and not connected by a
hose-set.
Refer to Technical Sheet for the position of connection.
The outlet connection is male thread R3/4" (20mm) and requires union connection to allow for removal of
the unit.
)RUXQLWVVHWDW&WKHGLVWDQFHWRWKH¿UVWRXWOHWPXVWEHDPLQLPXPRIPHWUHV
Keep the pipe lengths to a minimum and make sure that the pipework is well insulated, as correct
performance of the appliance is dependent on properly insulated pipework.
DO NOT FIT ANY VALVES OR RESTRICTORS TO THE OUTLET
OF THE WATER HEATER.
DO NOT FIT ANY OBSTRUCTION TO THE PRESSURE RELIEF LOCATED
ON THE HOT WATER OUTLET CONNECTION.
After purging the air from the system using the hot water supply taps, remove the water inlet strainer located
on the cold water supply inlet connection.
5HPRYHDQ\GHEULVIURPWKH¿OWHUDQGUHSODFH:KHQUHSODFLQJWKH¿OWHUGRQRWRYHUWLJKWHQWKH³2´ULQJVHDO