4.3.4 Installation of Pipe Hangers with Above-Ground Units

Trapzilla units installed indoors, above-ground require the use of pipe hangers (purchased separately) 

to properly support plumbing and reduce stress on connections with unit. Thermaco recommends the 

use of four (4) Zinc-plated Steel Loop Style hangers with 1000 lbs. work load limit for a single Trapzilla 

installation with two (2) hangers placed before inlet side cleanout and two (2) hangers placed after final 

cleanout. 
Place each pair of hangers 35” apart (space-permitting) and no closer than 5” from any joint. When 

multiple units are installed place one (1) additional pipe hanger in between each unit, leaving 5” distance 

from unit and cleanout. Follow pipe hanger manufacturer’s instructions for physical installation.

5. In-Ground Installation Instructions

5.1 Plumbing Instructions for Single TZ-1826 Installed In-Ground

A Trapzilla unit may also be installed in the ground inside or outside of the facility.  For instances 

where the facility drainage piping requires an extension collar that is more than the 18” provided 

by the built-in extension, the ECA-TZ-29 Extension Collar Assembly may be installed to align the 

Trapzilla inlet with the drainage piping.  Thermaco, Inc. strongly recommends surrounding the 

in-ground Trapzilla with concrete to provide additional structural strength and to offset buoyancy 

effects. For Buoyancy Calculations & suggested concrete fill quantities please see page 17.   

In-Ground Installations inside of a building must have a vessel vent installed and be piped to 

atmosphere.

Note: Drawing for reference only.  Equipment must be installed in compliance with all applicable laws, regulations 

and codes, including plumbing codes.  Installation should be performed by a qualified plumber. 

Outlet Vent -  

extend to grade 

and cover or con-

nect to facility

Vessel Vent -  

to atmosphere

Built-in 18”  

extension collars

Trapzilla cover -  

placed on top-most 

extension collar, to 

be accessible from 

ground level

Grade

Two-way cleanout 

before and after 

each unit, extend to 

grade.

Concrete surround-

ing unit body and 

extension collar.

Inlet

Outlet

5/8”-11 Rods

Loop-Style  

Pipe Hanger

35” between 

hangers

5” between hangers 

and any joints

Unit must be supported by 

Trapzilla Support Stand Assembly. 

No Trapzilla unit may be hung 

using pipe hangers.

Содержание Trapzilla TZ-1826

Страница 1: ...HOLE OR PART WITHOUT WRITTEN CONSENT FROM THERMACO INC POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREE...

Страница 2: ...There are many factors influencing odor evolution and dissemination These include room ventilation kitchen menu ambient temperatures ware washing practices grease oil input daily input fluid volume sa...

Страница 3: ...andard STC 22 cover Each TZ 1826 would require two 2 FTCA 22 covers SSA 1826 Support Stand for TZ 1826 forAbove Ground Installations Must be fully supported not to be installed over grates Included wi...

Страница 4: ...diameter of the system s outlet connection must be present as close as possible to the Trapzilla outlet to prevent possible siphonage problems The Vent on the Outlet piping is to be installed in accor...

Страница 5: ...ut before and after all Trapzilla Installations Outlet Inlet Cleanout Cleanout Outlet Vent Connect to facility vent Note Drawing for reference only Equipment must be installed in compliance with all a...

Страница 6: ...ts Connect to facility vent Low Head Flow Control not pictured to be installed as close as possible to inlet of first grease interceptor Cleanout Note Drawing for reference only Equipment must be inst...

Страница 7: ...ESS NOTED 646 GREENSBORO STREET PO BOX 2548 ASHEBORO NC 27203 VOICE 336 629 4651 FAX 336 626 5739 Decimals XX 03 XXX 015 Unless otherwise specified Dimensions are in inches Tolerances Angular 1 CHECKE...

Страница 8: ...it may also be installed in the ground inside or outside of the facility For instances where the facility drainage piping requires an extension collar that is more than the 18 provided by the built in...

Страница 9: ...s purchased separately In some cases TZ 1826 may be installed in locations where built in extension collar will not reach grade In these cases the two piece ECA TZ 29 Extension Collar purchased separa...

Страница 10: ...dapter ring Two of these screws should be installed in each of the four 4 skirt areas of the adapter ring Check the extension collar height dimension frequently during this operation to ensure that th...

Страница 11: ...bolts and fully remove the 22 lid to pump out It is not necessary to remove adapter lid to pump out Trapzilla 2 Begin by taking the grease from the top of the main chamber until all grease is removed...

Страница 12: ...not arising out of defects in workmanship or materials Thermaco shall not be responsible for damage to Products resulting from ultraviolet light exposure vault flooding sewer line back up pumping or...

Отзывы: