has some light carbon deposits, the burn out occurred 
while the compressor was not rotating. Contaminants are 
therefore largely confined to the compressor housing. A 
single installation of liquid and suction line filter/driers will 
probably clean up the system.

If sludge is evident in the discharge line, it will likely be found 
in the suction line. This indicates the compressor burned out 
while running. Sludge and acid has been pumped throughout 
the system. Several changes of the liquid and suction filter/
driers will probably be necessary to cleanse the system.

5.  Correct the system fault that caused the burn out. Consult 

the factory for advice.

6.  Install the replacement compressor with a new capacitor 

and an oversized liquid line filter. In a running burn 
out, install an oversized suction line filter/drier between 
the accumulator and compressor. Thoroughly flush the 
accumulator with refrigerant to remove all trapped sludge 
and to prevent the oil hole from becoming plugged. A 
standing burn out does not require a suction line filter/drier.

7.  Evacuate the system with a good vacuum pump and 

accurate vacuum gauge. Leave the pump on the system for 
at least an hour.

An alternate method of removing moisture and non-
condensibles from the system requires evacuation to 29” Hg 
vacuum. Then break the vacuum with 35 to 50 PSIG refrigerant 
vapor charge. Leave the vapor charge in the system from at 
least 5 minutes before removing it. Repeat the vapor charge/
wait/remove sequence twice more and then charge the system 
with the quantity and refrigerant listed on the nameplate.

8.  Operate the system for a short period of time, monitoring 

the suction pressure to determine that the suction filter 
is not becoming plugged. Replace the suction filter/drier 
if pressure drop occurs. If a severe running burn out has 
occurred, several filters/driers may have to be replaced to 
remove all of the acid and moisture.

NOTE: NEVER

 use the compressor to evacuate the system or any 

part of it.

5.6C Replacing a Compressor - Nonburn Out

Remove the refrigerant from the system. Replace the compressor 
and liquid line filter/drier. Charge the system to 50 PSIG and 
check for leaks. Remove the charge and weigh in the refrigerant 
quantity listed on the nameplate. Operate they system to verify 
performance.

5.7 Humidity Control

The humidity control is an adjustable switch that closes when the 
relative humidity of the air in which it is located rises to the dial 
set point. It opens when the RH drops 4 to 6% below the set point.

5.8 Defrost Thermostat

The defrost thermostat is attached to the refrigerant  
suction tube between the accumulator and compressor. It will 
automatically shut the compressor off if the low side  
refrigerant temperature drops due to excessive frost  
formation on the evaporator coil. The blower will continue  
to run, causing air to flow through the evaporator coil and melt the 
ice. When the ice has melted, the evaporator  
temperature will rise and the thermostat will restart the  
compressor.

5.9 Condensate Pump

Condensate is automatically pumped to a remote location when 
the water level in the pump’s reservoir rises to close the float 
switch.

SANTA FE INSTALLER'S AND OWNER'S MANUAL

6

Santa Fe Installer’s & Owner’s Manual

7

Santa Fe Installer’s & Owner’s Manual

Содержание Santa-Fe

Страница 1: ...ation operating and safety instructions warranty information and all ancillary products n Read and save these instructions For small usage P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www th...

Страница 2: ...Size Unit Size w o duct collars 20 W x 17 D x 36 H Weight 110 lbs 2 Installation 2 1 Location The Santa Fe can be installed in a variety of locations to meet the owner s needs as listed below In all...

Страница 3: ...e in 10 lengths from building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short pie...

Страница 4: ...apillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates The evaporator operates in a...

Страница 5: ...essor terminals C and R No continuity indicates an open run winding The compressor must be replaced Normal run winding resistance is 5 to 2 ohms 6 Compressor terminal C and overload terminal 1 No cont...

Страница 6: ...ystem with the quantity and refrigerant listed on the nameplate 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plu...

Страница 7: ...SANTA FE WIRING DIAGRAM 7 Santa Fe Installer s Owner s Manual Figure 2 Electrical Schematic of the Santa Fe Dehumidifier...

Страница 8: ...oil 10 4021409 1 Cord Wire Harness 11 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 11 12 4021395 1 Evaporator Coil 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain 56...

Страница 9: ...oving 6 screws 4 Remove the 4 screws securing the wiring box to the inside of the blower end of the dehumidifier and pull the box away from the cabinet to allow access 5 Insert a romex connector or co...

Страница 10: ...are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against the bottom of the pump re...

Страница 11: ...the inlet to the guides 4 Replace the filters in the unit Exhaust Collar Mounting Instructions 5 The six inch opening may be used as a fresh air inlet from outside 6 Remove the exhaust collar from the...

Страница 12: ...sher and 2 screws are not used on the Santa Fe Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Santa Fe Muffler Kit Installe...

Страница 13: ...anta Fe Installer s Owner s Manual Foam filter with plastic grid up Pleated filter with air flow arrow pointed down AIR FLOW Top of Dehumidifier Instructions To prevent damaging the foam filter place...

Страница 14: ...and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Страница 15: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680...

Отзывы: