2.1D In A Remote Area, Duct Outlet Only. 

A simpler remote installation method than above uses ducting 
between the Santa Fe discharge and the humid room; the 
Santa Fe inlet draws air from the room in which it’s located. 
This works well if there is an adequate air flow path between 
the two rooms; e.g. high door undercut, louvered door or wall 
grill. This eliminates the need to remote mount the humidity 
control. There are several potential disadvantages to using 
this method. First, humid air is drawn into the room where 
the Santa Fe is located. Second, to accurately sense humidity, 
the blower in the Santa Fe may need to run continuously to 
draw air from the humid room into the Santa Fe room. Third, a 
slight negative pressure is created in the room with the Santa 
Fe which could back draft open combustion devices located 
there. If such devices are present, call the factory for specific 
instructions before using this installation method or consider 
the option below.

2.1E In A Remote Area, Duct Inlet Only. 

When the Santa Fe is located in a room separate from 
the main area to be dehumidified, it may be desirable to 
dehumidify and/or slightly pressurize that room. Pressurization 
assures that open combustion devices do not back draft. This 
can be accomplished by installing a duct from the humid 
room to the Santa Fe inlet and by allowing the Santa Fe to 
discharge dehumidified air into the room in which it’s located. 
An adequate air flow path must exist between the two rooms 
for this method to work well. An additional humidity control may 
need to be mounted in the humid area and wired to the Santa 
Fe to accurately maintain the desired humidity. Local electrical 
codes must be followed when wiring the control.

2.2 Electrical Requirements

The Santa Fe plugs into a common grounded outlet on a 15 Amp 
circuit. It draws between 6 and 7 Amps under  normal operating 
conditions. If used in a wet area (pool, spa room, or basement 
prone to flooding), a ground fault interrupter protected circuit is 
required. 

2.3 Condensate Removal

Condensate drains by gravity via the clear hose extending from 
the unit. Route hose to a floor drain. Use care to keep the hose as 
flat to the floor as possible. Excessive humps or kinks will prevent 
proper drainage. 

If the Santa Fe is located too far from a floor drain for the attached 
hose to reach, 1/2” PVC pipe can be used to extend it. It is 
commonly available in 10’ lengths from building supply, plumbing 
and hardware stores. It will slide tightly inside the end of the drain 
hose. 

If more than one length of pipe is required they can be joined with 
a short piece cut from the end of the drain hose. 

2.4 Ducting

2.4A Optional Ducting 

An inlet shroud with an 8” round collar and an 8” round 
exhaust collar are available from the factory that will allow 
round ducting to be attached to the inlet and/or outlet of the 
Santa Fe.

2.4B Ducting for Dehumidification 

Ducting the Santa Fe as mentioned in sections 2.1B-2.1E 
requires consideration of the following points: 

 Duct Sizing:

 For total duct lengths up to 25 feet, use a 

minimum 8” diameter round or equivalent rectangular. For 
longer lengths, use a minimum 10” diameter or equivalent. 
Grills or diffusers on the duct ends must not excessively 
restrict air flow. 

Isolated Areas: 

Effective dehumidification 

may require that ducting be branched to isolated, stagnant 
areas. Use 6” diameter branch ducting to each of two or three 
areas, use 4” to each of four or more areas.

3. Operation

3.1 Humidity Control Adjustment

The dehumidifier will run continuously until relative humidity 
(RH) is reduced to the humidity control dial setting. Setting the 
humidity control to lower RH levels will 

NOT

 increase the unit’s 

dehumidification rate, it will simply run longer to reduce the 
area’s RH to the setting. The Santa Fe unit (and refrigerant based 
dehumidifiers in general) will reduce a warm space’s RH to a 
lower level than that of a cool space. For example, the Santa Fe 
may reduce an 80° F space to 30% RH. However, if the same 
space is 65° F, it may only reduce it to 40% RH. It is  therefore 
pointless to set the humidity control to excessively low levels 
in cool rooms. Doing so will result in long periods of ineffective 
dehumidifier run time. Quality humidity meters are available from 
the factory and are recommended to accurately monitor humidity 
levels.

3.2 Blower Switch

Turning “ON” the fan switch will cause the unit’s internal blower 
to run continuously, whether the unit is dehumidifying or not. This 
function is desirable if the unit is used for air circulation.

4. Maintenance

4.1 Air Filter

The Santa Fe is equipped with 2 air filters. A foam pre-filter 
followed by a standard MERV-11 65% efficient pleated fabric 
filter. These should be checked every six months. Operating 
the unit with dirty filters will reduce dehumidifier capacity and 
efficiency and may cause the compressor to cycle off and on 
unnecessarily on the defrost control.

SANTA FE INSTALLER'S AND OWNER'S MANUAL

2

Santa Fe Installer’s & Owner’s Manual

3

Santa Fe Installer’s & Owner’s Manual

Содержание Santa-Fe

Страница 1: ...ation operating and safety instructions warranty information and all ancillary products n Read and save these instructions For small usage P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www th...

Страница 2: ...Size Unit Size w o duct collars 20 W x 17 D x 36 H Weight 110 lbs 2 Installation 2 1 Location The Santa Fe can be installed in a variety of locations to meet the owner s needs as listed below In all...

Страница 3: ...e in 10 lengths from building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short pie...

Страница 4: ...apillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates The evaporator operates in a...

Страница 5: ...essor terminals C and R No continuity indicates an open run winding The compressor must be replaced Normal run winding resistance is 5 to 2 ohms 6 Compressor terminal C and overload terminal 1 No cont...

Страница 6: ...ystem with the quantity and refrigerant listed on the nameplate 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plu...

Страница 7: ...SANTA FE WIRING DIAGRAM 7 Santa Fe Installer s Owner s Manual Figure 2 Electrical Schematic of the Santa Fe Dehumidifier...

Страница 8: ...oil 10 4021409 1 Cord Wire Harness 11 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 11 12 4021395 1 Evaporator Coil 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain 56...

Страница 9: ...oving 6 screws 4 Remove the 4 screws securing the wiring box to the inside of the blower end of the dehumidifier and pull the box away from the cabinet to allow access 5 Insert a romex connector or co...

Страница 10: ...are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against the bottom of the pump re...

Страница 11: ...the inlet to the guides 4 Replace the filters in the unit Exhaust Collar Mounting Instructions 5 The six inch opening may be used as a fresh air inlet from outside 6 Remove the exhaust collar from the...

Страница 12: ...sher and 2 screws are not used on the Santa Fe Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Santa Fe Muffler Kit Installe...

Страница 13: ...anta Fe Installer s Owner s Manual Foam filter with plastic grid up Pleated filter with air flow arrow pointed down AIR FLOW Top of Dehumidifier Instructions To prevent damaging the foam filter place...

Страница 14: ...and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Страница 15: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680...

Отзывы: