Santa Fe HC Owners Manual

6.2 Blower (Fan) Switch

Turning “

ON

” the fan switch will cause the unit's internal

blower to run continuously, whether the unit is dehumidifying
or not. This function is desirable if the unit is used for air 
circulation.

Turning “

OFF

” the fan switch will cause the unit’s internal

blower to run only while the unit is dehumidifying.

7 Maintenance

NOTE: Do not operate the unit without the filter or with 
a less effective filter. The heat exchange coils inside
the unit could become clogged and require disassembly 
to clean.

7.1 Air Filter

The Santa Fe HC ships with a pleated fabric filter standard.
This should be checked monthly. Operating the unit with a
dirty filter will reduce dehumidifier capacity and efficiency
and may cause the compressor to cycle on and off unnecessarily. 

The pleated fabric filter can generally be vacuumed clean
several times before needing replacement. Replacement 
filters can be ordered from the factory. To order a replacement
filter, refer to the options and accessories table in this document.

7.2 Blower Oiling

The blower motor has been lubricated at the factory for many
years of normal operation.

8 Service

WARNING: Servicing the Santa Fe HC with its high 
pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, 
serious bodily injury, and/or property damage. Only 
qualified service people should service this unit.

8.1 Technical Description

The Santa Fe HC uses a refrigeration system similar 
to an air conditioner's to remove heat and moisture from
incoming air, and add heat to the air that is discharged. 
Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil. The refrigerant is cooled
and condensed by giving up its heat to the air that is about 
to be discharged from the unit. The refrigerant liquid then
passes through a filter/drier and capillary tubing which cause

the refrigerant pressure and temperature to drop. It next
enters the evaporator coil where it absorbs heat from the
incoming air and evaporates.

The evaporator operates in a flooded condition, which means
that all the evaporator tubes contain liquid refrigerant during
normal operation. A flooded evaporator should maintain 
constant pressure and temperature across the entire coil,
from inlet to outlet. The mixture of gas and liquid refrigerant
enter the accumulator after leaving the evaporator coil. The
accumulator prevents any liquid refrigerant from reaching the
compressor. The compressor evacuates the cool refrigerant
gas from the accumulator and compresses it to a high 
pressure and temperature gas to repeat the process.

8.2 Troubleshooting

No dehumidification, neither blower nor compressor run with
fan switch OFF. 
1. Unit unplugged or no power to outlet.
2. Humidity control set too high or defective.
3. Loose connection in internal wiring.

No dehumidification, compressor does not run but blower
runs with fan switch OFF and humidity control turned to ON.
1. Defective compressor or compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defrost thermostat open.

Blower runs with fan switch OFF, but compressor cycles on & off.
1. Low ambient temperature and/or humidity causing unit to

cycle through defrost mode.

2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.

Blower does not run with fan switch in either position.
Compressor runs briefly but cycles on & off.
1. Loose connection in blower circuit.
2. Obstruction prevents impeller rotation.
3. Defective blower.
4. Defective blower switch.

IMPORTANT

WARNING

Figure 16:

Santa Fe HC refrigeration system.

Figure 15:

Blower

fan switch.

Содержание Santa Fe HC

Страница 1: ...tion and air filtration True Performance Off the shelf appliance grade dehumidifiers rate their dehumidification capacities at 80 F 60 relative humidity RH The performance of these devices drops signi...

Страница 2: ...ed to be installed indoors only 1 Intended Application for Santa Fe HC For the ideal installation draw air from the central part of the home and return it to isolated areas of the home like the bedroo...

Страница 3: ...section 5 for attaching duct collars ducting 4 1C In A Remote Area Duct Inlet Outlet Fig 6 It is often desirable especially in recreational rooms and finished areas to install the Santa Fe HC in an a...

Страница 4: ...wiring the control 4 2 Remote Humidity Controls All remote humidity controls should be mounted in a central area of the the space to be dehumidified where it can accurately sense the humidity of the...

Страница 5: ...duct ends must not excessively restrict air flow Isolated Areas Effective dehumidification may require that ducting be branched to isolated stagnant areas Use 6 diameter branch ducting to each of two...

Страница 6: ...ensed by giving up its heat to the air that is about to be discharged from the unit The refrigerant liquid then passes through a filter drier and capillary tubing which cause the refrigerant pressure...

Страница 7: ...has melted the evaporator temperature will rise and the thermostat will restart the compressor 9 Service Parts List PART NO DESCRIPTION 4021395 Coil Evaporator 4021396 Coil Condenser 4021470 Thermost...

Страница 8: ...plies to residential applications and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repai...

Страница 9: ...Santa Fe HC Owners Manual 9...

Страница 10: ...produced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2004 Therma Stor LLC All rights reserved PO Box 8...

Отзывы: