1-877-420-1330
Quest 185 Cool
Installation, Operation and Maintenance Instructions
6
www.QuestHydro.com
Important Precautions
• The dehumidifier is designed to be installed indoors in a space that is protected from rain and flooding.
• Install the dehumidifier with enough space to access the back and side panels for maintenance and service.
• Avoid directing the discharge air at people.
• If used near a water source; be certain there is no chance the dehumidifier could fall into the water or get splashed and that it is
plugged into a dedicated circuit and Ground Fault Circuit Interrupter (GFCI) protected outlet.
• DO NOT use the dehumidifier as a bench or table.
• DO NOT place the dehumidifier directly on structural building members without vibration absorbers or unwanted noise may result.
Place the dehumidifier on supports to raise the base of the unit.
• A drain pan MUST be placed under the dehumidifier if installed above a living area or above an area where
water leakage could cause damage.
Location Considerations
• Allow sufficient clearance to handle the unit’s overall dimensions as well as the necessary return and supply ductwork to the unit.
• Allow sufficient clearance for filter removal and to prevent airflow obstruction.
• Electrical service access will require the removal of a side panel. Allow sufficient clearance on a side of the unit.
• Locate the dehumidifier in an area where the cord’s length (10') easily reaches a 115 VAC electrical outlet with a minimum of a 15
Amp circuit capacity.
• Locate the dehumidifier in an area where field wiring the control (low voltage) to the unit will be possible.
• It is recommended that a backdraft damper be used in the discharge duct of the dehumidifier, especially
when connecting to the supply
ducting system. The backdraft damper prevents supply air from counter flowing through the
dehumidifier when it is not
operating. The dehumidifier’s
location should be chosen to
allow installation of this accessory
if necessary.
• The dehumidifier may be suspended from structural members with steel hanger straps or a suitable
alternative, ensuring the assembly
supports the dehumidifier’s base
in its entirety. DO NOT hang the dehumidifier from its cabinet.
• Allow for proper routing and drainage of needed drain pipes.
DEHUMIDIFIER SET UP
Содержание Quest 185 Cool
Страница 26: ...1 877 420 1330 www questhydro com...