Quest 185 Cool 

Installation, Operation and Maintenance Instructions

22

www.QuestHydro.com

[email protected]

 

Symptom 

Possible Reason 

Troubleshooting Procedure

 

 

CAUTION!

TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.

Troubleshooting

Troubleshooting Procedure for Control  

Related Issues
This method of diagnosis will test the 3 main components 

of the control circuit individually to indicate any poten-

tial problems. This is to be used when the control will not 

activate the main unit.
1.  Detach field control wiring connections from the 

pigtails on the main unit.

2.  Connect the yellow and green wire pigtails  

together; only the fan should run. Disconnect the 

wires.

3.  Connect the yellow and blue wires pigtails together; 

fan and compressor should run.  

Disconnect the wires.

4.  If this test works, the main unit is working  

correctly from a control standpoint. 

5.  Reconnect field control wiring to the pigtails on the 

main unit.

6.  Remove the control panel cover and detach the field 

wiring from the control connections. 

7.  Connect the yellow and green wires together; only the 

fan should run. Disconnect the wires.

8.  Connect the yellow and blue wires together; fan and 

compressor should run. Disconnect the wires.

9.  If this test works, then the field control wiring is ok.
10.  If the problem persists, then the control is most 

likely faulty.

  

 

WARNING!

 

ELECTRICAL SHOCK HAZARD:  

ELECTRICAL POWER MUST BE PRESENT 
TO PERFORM SOME TESTS. THESE TESTS 
SHOULD BE PERFORMED BY A QUALIFIED 
SERVICE PERSON.

Neither fan nor com-

pressor  

running.  

Dehumidification  

is being called for.

Compressor is  

not running.  

Dehumidification  

is being called for. Fan 

is running.

1.  Defective compressor run 

capacitor.

2.  Loose connection in com-

pressor circuit.

3.  Defective compressor 

overload.

4.  Defective compressor.
5.  Defrost thermostat open.

Compressor cycles on 

and off. Dehumidifi-

cation is being called 

for.

1.  Low ambient  

temperature and/or  

humidity causing unit  

to cycle through  

defrost mode.

2.  Defective compressor 

overload.

3.  Defective compressor.
4.  Defrost thermostat  

defective.

5.  Dirty air filter(s) or air flow 

restricted.

6. Defective fan or relay.

1.  Dehumidifier unplugged  or 

    no power to outlet.

2.  Humidity control set  

too high.

3.  Loose connection in  

internal or control wiring.

4.  Defective compressor relay.
5.  Defective control  

transformer.

SERVICE

Содержание Quest 185 Cool

Страница 1: ...eat load generated from dehumidifying the room to be released in the outside condensing unit thus eliminating the need for additional cooling and reducing air conditioner run time Installation Instruc...

Страница 2: ...7 Condensate Removal 8 Hanging Install Diagram 8 Ducting 8 Dehumidifier Electrical Requirements 9 Condensing Unit Electrical Requirements 10 Condensing Unit Dehumidifier Wiring 11 Line Set Installati...

Страница 3: ...THE POWER CORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR A SIMILARLY QUALIFIED PERSON IN ORDER TO AVOID A HAZARD THIS APPLIANCE IS NOT INTENDED FOR USE BY PERSONS INCLUDI...

Страница 4: ...4 Embossed Pleat will need filter housing Efficiency 95 ASHRAE Dust Spot Size 20 x 24 x 4 Power Cord 10 115 VAC Ground Internal Insulated Cabinet Yes Drain Connection 3 4 Threaded Female NPT Refrigera...

Страница 5: ...p Kit 4036685 Hang Kit 4025287 MERV 14 Filter Housing 4024370 MERV 14 Filter 20 x24 x4 4029087 MERV 14 Filters 3 Pack 4023672 6 Motorized Damper 4026859 6 Flex Duct 25 4020128 6 Flex Insulated Duct 25...

Страница 6: ...icient clearance to handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal and to prevent airflow obstructio...

Страница 7: ...nd that it is plugged into a dedicated circuit and Ground Fault Circuit Interrupter GFCI protected outlet DO NOT use the condensing unit as a bench or table DO NOT place the condensing unit where the...

Страница 8: ...re the feet are extended such that the dehumidifier is 2 1 2 off the ground Then coil the drain hose under itself or position a spacer to lift the hose 1 off the ground after the hose has touched the...

Страница 9: ...5 BLK 2 BLU 2 115V 24V COM COM BRN 3 BLK 1 BLK 1 24VAC DEHU FAN COM CUSTOMER CONTROL WIRING BLU YEL GRN RED BLK BLK 24VACTO COND GRN 4 NO BLK 5 VIO 6 CAUTION DO NOT ALLOW THE YELLOW LEAD TO CONTACT TH...

Страница 10: ...ain Relief Block Power Supply Unit wire harness 1 Take off the panel top by removing the one screw that secures it to the condensing unit 2 Loosen the two strain relief block screws 3 Insert the power...

Страница 11: ...COIL DEFROST T STAT L PRESS SWITCH RUN CAP 24VAC SIGNAL FROM DEHU NC NO YEL 6 BLU 7 GRN 5 PNK 3 WHT 4 RED 1 YEL 2 BLK 9 BLK 8 BLK BLK BLK 3 WHT 5 BLK 2 BLU 2 115V 24V COM COM BRN 3 BLK 1 BLK 1 24VAC D...

Страница 12: ...must supply a line set 1 4 liquid line 3 8 gas line suitable for use with R410a refrigerant to connect the indoor unit to the outdoor unit The maximum allowable length of the line set is 50 feet The...

Страница 13: ...ent water condensation on the gas line Flush the lines with an inert gas before and or during brazing to prevent oxidation inside the lines Release the inert gas holding charge and remove the plugs in...

Страница 14: ...E SHIELD TO PROTECT AGAINST BURNS WASH HANDS WITH SOAP AND WATER AFTER HANDLING BRAZING ALLOYS AND FLUX TO PREVENT STRIPPING OF THE VARIOUS CAPS USED THE APPROPRIATELY SIZED WRENCH SHOULD BE USED AND...

Страница 15: ...urr the cut ends of the line set lines 2 Fit the line stubs with flare fittings included with the condensing unit onto the line set if necessary 3 Swage the liquid and gas lines if necessary to fit on...

Страница 16: ...re hose to the service port on the gas line will protect the manifold gage set from high pressure damage during leak testing Cap liquid line service port 2 Make sure all of the valves on the manifold...

Страница 17: ...ssure indicates a leak in the system If this occurs check the manifold gage set hoses tee and valve core removal tools for leaks If no leak is found repeat the leak test procedure on Page 15 10 Evacua...

Страница 18: ...line stub valve core removal tool 6 Open the low pressure side of the manifold gage set and weigh in the amount of HFC 410A calculated in step 1 7 Close the valve on the HFC 410A cylinder and the low...

Страница 19: ...USED OR DAMAGE TO THE TRANSFORMER WILL RESULT Control Connections The control and the control wires leaving the Quest 185 Cool are numbered and color coded to prevent confusion Depending on the contro...

Страница 20: ...white White 24 VAC power transformer neutral side common with red Yellow Transformer high side Five Color Coded Wires Control Operation Unit ON Fan ON Make contact between yellow and blue wires Unit O...

Страница 21: ...eft in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type SERVICE Service Parts List Dehumidifier Item Par...

Страница 22: ...and green wires together only the fan should run Disconnect the wires 8 Connect the yellow and blue wires together fan and compressor should run Disconnect the wires 9 If this test works then the fie...

Страница 23: ...re is 55 degrees or below and or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of perform...

Страница 24: ...e Reason Troubleshooting Procedure CAUTION TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN Troubleshooting Troubleshooting Procedure for Condenser Relating Issues WARNING ELECTRICAL...

Страница 25: ...ited warranty does not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Produc...

Страница 26: ...1 877 420 1330 www questhydro com...

Отзывы: