Therma-Stor Quest 185 Cool Скачать руководство пользователя страница 15

1-877-420-1330

Quest 185 Cool 

Installation, Operation and Maintenance Instructions

15

www.QuestHydro.com

[email protected]

LINE SET INSTALLATION

 

CAUTION!

THE DEHUMIDIFIER IS SHIPPED FROM THE FACTORY PRESSURIZED WITH A CHARGE OF  

INERT GAS AND WITH RUBBER PLUGS IN THE LINES. PURGE THE INERT GAS FROM THE  

DEHUMIDIFIER BY REMOVING THE RUBBER PLUGS IN THE LIQUID AND GAS LINES TO  

RELEASE THE INERT GAS BEFORE CONNECTING THE LINE SET.

Use the following procedure to connect the line set to the Dehumidifier:

1.  Purge the inert gas from the dehumidifier by removing the rubber plugs in the liquid and gas lines to release the inert gas before 

connecting the line set.

2.  Place a field-provided heat shield, such as a wet rag, against the dehumidifier and around the piping stubs. The heat shield must 

be in place to protect the cabinet from heat damage.

3.  Swage the liquid and gas lines (if necessary) to fit onto the dehumidifier lines.

4.  Purge the dehumidifier lines and the line set with dry nitrogen (Inert gas) to prevent oxidation during brazing. Flow dry nitrogen 

into the lines at a low pressure of 1 to 2 psig.

5.   Braze the line set lines to the dehumidifier lines.

6.  Remove the heat shield after brazing and allow the connections to cool.

Use the following procedure to connect the line set to the Condensing Unit:

1.  Cut the line set lines to the proper required length. Deburr the cut ends of the line set lines.

2.  Fit the line stubs with flare fittings (included with the condensing unit) onto the line set if necessary.

3.  Swage the liquid and gas lines (if necessary) to fit onto the line stubs with the flare fittings.

4. Remove service valve caps and cores.

5.  Purge the lines with dry nitrogen (Inert gas) to prevent oxidation during brazing.

6. Braze the line set lines to the line stubs.

7.  Apply a light coating of refrigeration oil to the flare fitting threads on the condensing unit valves.

8.  Start each flare nut on the corresponding flare fitting on the condensing unit valves by hand, making sure the threads are prop-

erly engaged. Tighten the flare nuts hand tight.

9.  Carefully torque the flare nuts to the corresponding flare fittings on the condensing unit valves.

•  Torque the liquid line flare  

nut to 13.3 ft-lbs.

•  Torque the suction line  

flare nut to 30.1 ft-lbs.

10.  Reinstall service valve  

cores and caps.

Note – If there is no pressure in the dehumidifier when the first plug is removed, check the dehumidifier for damage and 

leaks before continuing with the installation.

Note: Alternately, the stubs with the 

flare fittings can be connected to the 

condensing unit before brazing the 

line set. In this case a field provided 

heat shield, such as a wet rag, must be 

placed over the flare fittings and valves 

on the condensing unit to protect them 

from heat damage. The service valve 

cap and core should be removed before 

brazing near  

stub tubes.

3-WAY VALVE

2-WAY VALVE

LIQUID LINE STUB

GAS LINE
STUB

SERVICE VALVE CAPS

VALVE ROD CAPS

VALVE STEMS

Содержание Quest 185 Cool

Страница 1: ...eat load generated from dehumidifying the room to be released in the outside condensing unit thus eliminating the need for additional cooling and reducing air conditioner run time Installation Instruc...

Страница 2: ...7 Condensate Removal 8 Hanging Install Diagram 8 Ducting 8 Dehumidifier Electrical Requirements 9 Condensing Unit Electrical Requirements 10 Condensing Unit Dehumidifier Wiring 11 Line Set Installati...

Страница 3: ...THE POWER CORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR A SIMILARLY QUALIFIED PERSON IN ORDER TO AVOID A HAZARD THIS APPLIANCE IS NOT INTENDED FOR USE BY PERSONS INCLUDI...

Страница 4: ...4 Embossed Pleat will need filter housing Efficiency 95 ASHRAE Dust Spot Size 20 x 24 x 4 Power Cord 10 115 VAC Ground Internal Insulated Cabinet Yes Drain Connection 3 4 Threaded Female NPT Refrigera...

Страница 5: ...p Kit 4036685 Hang Kit 4025287 MERV 14 Filter Housing 4024370 MERV 14 Filter 20 x24 x4 4029087 MERV 14 Filters 3 Pack 4023672 6 Motorized Damper 4026859 6 Flex Duct 25 4020128 6 Flex Insulated Duct 25...

Страница 6: ...icient clearance to handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal and to prevent airflow obstructio...

Страница 7: ...nd that it is plugged into a dedicated circuit and Ground Fault Circuit Interrupter GFCI protected outlet DO NOT use the condensing unit as a bench or table DO NOT place the condensing unit where the...

Страница 8: ...re the feet are extended such that the dehumidifier is 2 1 2 off the ground Then coil the drain hose under itself or position a spacer to lift the hose 1 off the ground after the hose has touched the...

Страница 9: ...5 BLK 2 BLU 2 115V 24V COM COM BRN 3 BLK 1 BLK 1 24VAC DEHU FAN COM CUSTOMER CONTROL WIRING BLU YEL GRN RED BLK BLK 24VACTO COND GRN 4 NO BLK 5 VIO 6 CAUTION DO NOT ALLOW THE YELLOW LEAD TO CONTACT TH...

Страница 10: ...ain Relief Block Power Supply Unit wire harness 1 Take off the panel top by removing the one screw that secures it to the condensing unit 2 Loosen the two strain relief block screws 3 Insert the power...

Страница 11: ...COIL DEFROST T STAT L PRESS SWITCH RUN CAP 24VAC SIGNAL FROM DEHU NC NO YEL 6 BLU 7 GRN 5 PNK 3 WHT 4 RED 1 YEL 2 BLK 9 BLK 8 BLK BLK BLK 3 WHT 5 BLK 2 BLU 2 115V 24V COM COM BRN 3 BLK 1 BLK 1 24VAC D...

Страница 12: ...must supply a line set 1 4 liquid line 3 8 gas line suitable for use with R410a refrigerant to connect the indoor unit to the outdoor unit The maximum allowable length of the line set is 50 feet The...

Страница 13: ...ent water condensation on the gas line Flush the lines with an inert gas before and or during brazing to prevent oxidation inside the lines Release the inert gas holding charge and remove the plugs in...

Страница 14: ...E SHIELD TO PROTECT AGAINST BURNS WASH HANDS WITH SOAP AND WATER AFTER HANDLING BRAZING ALLOYS AND FLUX TO PREVENT STRIPPING OF THE VARIOUS CAPS USED THE APPROPRIATELY SIZED WRENCH SHOULD BE USED AND...

Страница 15: ...urr the cut ends of the line set lines 2 Fit the line stubs with flare fittings included with the condensing unit onto the line set if necessary 3 Swage the liquid and gas lines if necessary to fit on...

Страница 16: ...re hose to the service port on the gas line will protect the manifold gage set from high pressure damage during leak testing Cap liquid line service port 2 Make sure all of the valves on the manifold...

Страница 17: ...ssure indicates a leak in the system If this occurs check the manifold gage set hoses tee and valve core removal tools for leaks If no leak is found repeat the leak test procedure on Page 15 10 Evacua...

Страница 18: ...line stub valve core removal tool 6 Open the low pressure side of the manifold gage set and weigh in the amount of HFC 410A calculated in step 1 7 Close the valve on the HFC 410A cylinder and the low...

Страница 19: ...USED OR DAMAGE TO THE TRANSFORMER WILL RESULT Control Connections The control and the control wires leaving the Quest 185 Cool are numbered and color coded to prevent confusion Depending on the contro...

Страница 20: ...white White 24 VAC power transformer neutral side common with red Yellow Transformer high side Five Color Coded Wires Control Operation Unit ON Fan ON Make contact between yellow and blue wires Unit O...

Страница 21: ...eft in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type SERVICE Service Parts List Dehumidifier Item Par...

Страница 22: ...and green wires together only the fan should run Disconnect the wires 8 Connect the yellow and blue wires together fan and compressor should run Disconnect the wires 9 If this test works then the fie...

Страница 23: ...re is 55 degrees or below and or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of perform...

Страница 24: ...e Reason Troubleshooting Procedure CAUTION TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN Troubleshooting Troubleshooting Procedure for Condenser Relating Issues WARNING ELECTRICAL...

Страница 25: ...ited warranty does not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Produc...

Страница 26: ...1 877 420 1330 www questhydro com...

Отзывы: